WIRING

The OP121/OH121  should  be  connected  as  shown  in  Figure  3  using  the  separate mounting  base, Model  DB-11.
Follow the control panel wiring connection drawing installed on the inside face of each control panel cover. See DB-
11 instruction, P/N 315-094193, for base mounting. Duplicate wiring information is also in the Installation, Operation,
and Maintenance Manual provided with every control panel.

Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for
each circuit.

WARNING!

Connect detector only to control units specified in detector and panel literature or system may
not operate.

AVERTISSEMENT!

Connectez le détecteur uniquement aux unités de contrôle spécifiées dans la documentation du
détecteur et de la centrale, faute de quoi le système pourrait ne pas fonctionner.

Figure 3

Wire size: maximum 14 AWG, minimum 18 AWG (Wire larger than 14 AWG can damage the
connector)

DETECTOR MOUNTING

TO INSTALL:

Rotate  detector  counterclockwise  while  gently
pressing on it until the detector seats fully into base.

Then rotate the detector clockwise until it stops and
locks  in  place.  Insert  optional  locking  screw  (Order
Model LK-11).

TO REMOVE:

Loosen  locking  screw,  if  installed.  Then  rotate  the
detector counterclockwise until stop is reached.

 

Pull detector out of base.

Under  no  circumstances  is  the  detector  head  to  be
disassembled.
No repairs should be attempted.

DO NOT PAINT

The detector is marked DO NOT PAINT. This is intended
to  prohibit  painting  during  routine  maintenance  of  the
occupancy  which  can  affect proper  operation  of  the
detector.

LED INDICATOR OPERATION

The OP121/OH121 contains an LED indicator capable of
flashing either one of three distinct colors: green, yellow,
or red. The microprocessor-based detector monitors the
following:

 

Smoke in its sensing chamber

Smoke sensitivity is within the range indicated on the
nameplate label

 

Internal sensors and electronics

Based on the results of the monitoring, the LED indicator
flashes the following:

Flash
Color

Condition

Flash  Interval
(Seconds)

Green

Normal supervisory operation. Smoke
sensitivity is within rated limits.

10

Yellow

Detector  is in trouble and needs
replacement.

5

Red

Alarm

2.5

No
Flashes

Detector not powered properly.
Installation check or device
replacement is needed

To initiating
circuit of Siemens
compatible
control unit

See remote device instructions
for wiring details

DB-11/DB-11E

[No remote device]

+

1a

5

1b

6

Do not use looped wire under base
terminal 5. Break wire run to provide
supervision of connection.

End of line
device
(note polarity
when applicable)

DB-11/DB-11E

[With remote device(s)]

1b

5

Device

RLC-11, RLW-11
ADB-11

Installation instructions

P/N 315-094925
P/N 315-096162

+

If remote devices are supported by the initiating circuit, each
detector/base may have up to 2 remote devices with the following
configurations and restrictions only:

Multiple remote devices

Remote device 1

RLC-11, RLW-11
RLC-11, RLW-11

Remote device 2

RSAC-11, RSAW-11
RLC-11, RLW-11

Restrictions

Wire from base to
RSAC-11/RSAW-11 to RL-11

1b

5

6

See 1)

1)

Summary of Contents for OP121

Page 1: ... with STI Mechanical Protection Guard Model STI 9604 see www sti usa com for details Electrical Voltage 16 27 VDC Ripple 3 V peak to peak Supervisory Current 100 μA max Alarm Current 30 50 mA Start up Time 30 seconds max DO NOT install this detection device until all construction is completed DO NOT store this detection device where it can be contaminated by dirt dust or humidity DETECTOR PLACEMEN...

Page 2: ... The detector is marked DO NOT PAINT This is intended to prohibit painting during routine maintenance of the occupancy which can affect proper operation of the detector LED INDICATOR OPERATION The OP121 OH121 contains an LED indicator capable of flashing either one of three distinct colors green yellow or red The microprocessor based detector monitors the following Smoke in its sensing chamber Smo...

Page 3: ...mal 30 seconds per applied setting Open area Green 10 double flash Air duct Green 10 triple flash TESTING AND MAINTENANCE To assure proper operation of the detector and control panel it is required that both the Sensitivity test and the Functional test be conducted using the procedures outlined below SENSITIVITY TEST The OP121 OH121 monitors its smoke sensitivity automatically and requires no test...

Page 4: ...36866 FDBZ492 PR A6V10330327 FCC Statement WARNING Installation and usage of equipment not in accordance with instructions manual may result in Radiation of radio frequency energy Interference to radio communications Install and use equipment in accordance with installation instructions manual Read the following information AVERTISSEMENT L installation et l utilisation d équipement non conforme au...

Reviews: