6
A6V10324661_en--_m
Recommended Detector Wall Mounting / Detector Guard Orientation
1. Mount box on wall with exterior mounting holes (1) in upper left and lower right position.
2. Mount detector base to 4-inch square box with locking hole (2) on left top.
3. When 4-inch square box and detector base are mounted as shown, detector LED will be in recommended 0°
position with detector inserted in base. When mounting the STI-9604 mechanical guard (3) on wall or ceiling, use
orientation indicated.
Figure 4
SMOKE DETECTOR FUNCTIONAL TEST (SMOKE
TEST GAS)
The fire control panel must be programmed to test mode
prior to performing a functional (* Go-No-Go) smoke
entry test. Failure to do so may result in a test failure.
Refer to the specific control panel installation operations
manual for proper “test mode” programming instructions.
To determine how to put the control panel in “test mode”,
specific programming instructions are located in the
panel documentation.
To activate the detector with test gas, only use the
following test gases:
·
HSI SmokeCheck™ testgas P/N HO-25S
·
HSI PurCheck P/N HO-30S
·
Smoke Sabre Smoke Detector Tester P/N
SMOKESABRE-01-001
·
Solo A5 Smoke Detector Tester Gas
P/N SOLOA5-001
·
Testifire 1001 / 2001 P/N TS3-001
Strictly follow the testing instructions provided on the gas
canister label. After applying the test gas for 1-2
seconds, the smoke alarm will occur within 4-10
seconds. If not, check the Test Mode and repeat the test.
Do not repeat the test multiple times or apply the test gas
too long – this will cause CO-troubles.
CAUTION
DO NOT use at distances smaller than 2 feet (0.6 m)
from detector. Spray the test gas for a period of 1-2
seconds. Excessive spraying may affect the detector’s
sensitivity and cause CO sensor troubles.
* This test is simply used to ensure that smoke can enter
the sensing chamber and alarm the control panel when
the detector reaches the programmed obscuration
(concentration) level.
CAUTION
DO NOT use any test gas other than the one mentioned
above as compatibility to the CO sensor cannot be
assured.
CO DETECTOR FUNCTIONAL TEST (CO TEST GAS)
The fire control panel must be programmed to test mode
prior to performing a functional (* Go-No-Go) CO gas
entry test. Failure to do so may result in test failure. Refer
to the specific control panel installation operations
manual for proper “test mode” programming instructions.
To determine how to put the control panel in “test mode”,
specific programming instructions are located in the
panel documentation.
Test by activating the detector using the approved CO
test gases:
·
Siemens CO Test Gas P/N 500-650053
·
SDI Solo C3 or C6, P/N SOLOC3-001, SOLOC6-001
·
HSI CO Check, P/N HO-CO2S
·
Testifire 1001 / 2001 P/N TC3-001
Following the instructions with product and provided on
the CO gas canister label. Spray the CO gas stream into
the detector opening from the opposite side of the alarm
indicator LED a distance of approximately 2 inches
(5 cm) from the CO sensor to the straw of the test gas
can is required. Use only short (approx. 1-2 seconds,
BUT NOT LONGER THAN 2 seconds) activation of the
gas can. After applying the test gas for 1-2s, the CO
alarm will occur within 4-10 seconds. If not, please check
the Test Mode again and repeat the test. Do not repeat
the test multiple times or apply the test gas too long –
this will cause CO-troubles.
* This test is simply used to ensure that a CO gas can
reach the CO sensor and alarm the control panel when
the detector reaches the programmed obscuration
(concentration) level.
The OOHC941 detectors can also be tested individually
using the DPU. Refer to the DPU Manual, P/N 315-
033260.
0°
1
2
3