DETECTOR TESTING
Only qualified service personnel should test. To assure
proper operation of the detector, both the Sensitivity and
Functional Test should be conducted. The minimum test
schedule may be found in the current edition of NFPA 72.
The CO sensor of the OOHC941 has a 10-year lifetime
from the date of installation.
SENSITIVITY MEASUREMENT
The sensitivity of OOHC941 detectors can be tested
individually using the DPU. Refer to the DPU Manual,
P/N 315-033260. The sensitivity can be measured by the
panel. Follow the instructions of the panel used.
Polarity insensitive wiring:
Figure 2
Isolator mode wiring:
Figure 3
Wire size: maximum 14 AWG, minimum 18 AWG (Wire larger than 14 AWG can damage the connector)
FROM ADDRESSABLE
DEVICE CIRCUIT OF A
COMPATIBLE CONTROL
UNIT OR PREVIOUS
ADDRESSABLE DEVICE
OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
8727W / 8727C /
RL-HW / RL-HC
TO NEXT BASE
TO NEXT BASE
DO NOT USE AN
END OF LINE DEVICE
DETECTOR BASE
MODEL DB-11/DB-11E
LINE 1 *
LINE 2 *
5
6
1a
TB1
TB3
TB2
1b
5
6
1a
1b
** The relay contacts are shown after System reset, which represents the non-alarm condition.
* OOHC941 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.
5
NO
C
NC
6
SUPERVISED AND POWER LIMITED
RELAY
**
CONTACTS
3A, 120 VAC
3A, 30 VDC
DO NOT USE AN
END OF LINE DEVICE
OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
8727W / 8727C /
RL-HW / RL-HC
TO NEXT BASE
TO NEXT BASE
DO NOT USE AN
END OF LINE DEVICE
DETECTOR BASE
MODEL DB-11/DB-11E
LINE 1
LINE 2
5
6
1a
TB1
TB3
TB2
1b
5
6
1a
1b
* The relay contacts are shown after System reset, which represents the non-alarm condition.
5+
NO
C
NC
6-
RELAY
*
CONTACTS
3A, 120 VAC
3A, 30 VDC
DO NOT USE AN
END OF LINE DEVICE
+
+
–
–
To initiating circuit of
SIEMENS compatible control unit