NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
7
NXAirS description
7. Panel construction
6.5 Bus sectionalizer
A bus sectionalizer consists of 2 modules:
One circuit-breaker module panel and one disconnecting module used as bus riser panel.
●
Busbar
●
Withdrawable unit
●
Disconnecting module
●
Low-voltage plug connector with mechanical interlock between module and panel
●
Busbar in the cable Connection compartment
●
2 or 3 CT
●
2 or 3 PT
Basic components
Option
Basic components
●
Enclosure made of bended galvanized steel-sheet
●
Door of the HV compartment is powder-coated with epoxy resin
●
Individual, self-supporting, modular compartments in solid-wall design
●
Compartments are bloted together
●
The sheet between compartments can withstand pressure of arcing
●
Each compartment relieves pressure upwards
1.
Low-voltage plug connector
2.
Drive and interlock unit of the circuit--Breaker
3.
Vacuum interrupter
4.
Fix and move contact
5.
The operation mechanism of circuit-breaker and
earthing switchgear, and Interlock device
6.
Making proof earthing switch
7.
4 cables per phase connecting
8.
Current transformer
9.
Contact box
10.
Busbar
11.
Pressure release channel
A.
HV compartment
B.
Busbar compartment
C.
Connection compartment
D.
Circuit--Breaker module compartment
E.
Low- voltage compartment
Figure 2.
cutaway view of the panel construction