NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
11
NXAirS description
10. Technical data
10.1 Panel
Electrical data (maximum values)
Rated voltage
12kV
Rated power-frequency withstand voltage
42kV
Rated lightning impulse withstand voltage
75kV
Rated frequency
50Hz
Rated short-circuit breaking current
25kA, 31.5kA, 40kA
Rated short-circuit making current
63kA, 80kA, 100kA
Rated peak withstand current
63kA, 80kA, 100kA
Rated short-time withstand current and time
25kA/4s, 31.5kA/4s, 40kA/4s
Rated current of the busbar
(
max.
)
4000A
Rated current of the feeder
(
max.
)
4000A
The highest ambient temperature
40°C
Width
Circuit breaker panel
l
k
≤
31.5kA l
n
≤
3150A
800
l
k
≤
40kA l
n
≤
2500A
800
l
k
= 40kA l
n
≥
3150kA
1000
Disconnecting panel
l
k
≤
31.5kA l
n
≤
3150A
800
l
k
≤
40kA l
n
≤
2500A
800
l
k
≤
40kA l
n
≥
3150A
Panel
1000
Substation transformer
1000
metering Panel
800
Height
l
k
≤
31.5kA l
n
≤
2500A
2200
l
k
= 31.5kA l
n
= 3150A
2400
l
k
= 40kA
2300
Depth
l
k
= 31.5kA l
n
= 3150A l
b
= 3150A
1500
l
k
≤
31.5kA l
n
≤
2500A l
b
≤
2500A
1350
l
k
≤
31.5kA l
n
≤
3150A l
b
≥
3150A
1500
l
k
= 40kA
1500
Height
Minimum dimension
2800
Width(operation area)
Minimum dimension for 800 width panel
1350
Minimum dimension for 1000 width panel
1550
Standard
IP4X
Option (only for the panel without natural ventilation)
IP51
IEC/EN standard
GB standard
Panel
60694
GB/T11022
62271-200
GB3906
Switchgear
Circuit breaker
62271-100
GB1984
Disconnector and earthling switch
62271-102
GB1985
Switch-disconnector
60265-1
GB3804
Insulation test
60071
GB311.1
Protection degree
60529
GB4208
Transformer
Current transformer
60044-1
GB1208
Potential transformer
60044-2
GB1207
Dimensions per panel in mm
Dimensions of the power
distribution room in mm
Protection degree
Basic regulation and standard
Standards for indoor used circuit-
breaker module panel NXAirS