NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
35
No.
Phenomenon
Cause
1
Manual operation is available for the
cassettee but electric operation is
impossible
1. The handle is inserted in the cassettee, not taken
out yet.
2. Locking conditions of electric cassettee are not met,
for example, position switch is not switched over.
3. Secondary wiring is incorrect, communication
wiring is reversed.
2
Manual operation is available for the
earthing switch but electric operation
is impossible
1. The circuit breaker is not fully in the test position.
2. Rear door of the cable compartment is not closed.
3. Secondary wiring is incorrect.
Possible phenomena in the
operation process:
If the problem still exists after inspection according to the above-mentioned causes, please contact
the manufacturer.