background image

3

3.  

.  IIN

NS

ST

TA

AL

LL

LA

AT

TIIO

ON  

N  

–  

–  

M

MIID

DIIM

MA

AS

ST

TE

ER  

R  

V

Ve

ec

ctto

orr

E

En

ng

glliis

sh

h

 © Siemens plc 1999

 © Siemens plc 1999

G85139-H1751-U529-D1

G85139-H1751-U529-D1

25

25

4/8/99

4/8/99

3. 

3. 

INSTALLATION 

INSTALLATION 

- MIDIMASTE

- MIDIMASTE

R Vector 

R Vector 

3.1 

3.1  Mechanical 

Mechanical Installation

Installation

WARNING

WARNING

THIS EQUIPMENT MUST BE EARTHED.

THIS EQUIPMENT MUST BE EARTHED.

This equipment must

This equipment must

not

not

 be energised with the cover removed.

 be energised with the cover removed.

To guarantee the safe operation of the equipment it must be installed and commissioned properly

To guarantee the safe operation of the equipment it must be installed and commissioned properly
by qualified personnel in compliance with the warnings laid down in these operating instructions.

by qualified personnel in compliance with the warnings laid down in these operating instructions.

Take particular note of the general and regional installation and safety regulations regarding work

Take particular note of the general and regional installation and safety regulations regarding work
on high voltage installations (e.g. VDE), as well as the relevant regulations regarding the correct

on high voltage installations (e.g. VDE), as well as the relevant regulations regarding the correct
use of tools and personal protective gear.

use of tools and personal protective gear.

Mount the inverter vertically to a flat, non combustible surface. Make sure that the unobstructed

Mount the inverter vertically to a flat, non combustible surface. Make sure that the unobstructed
clearance for each of the cooling inlets and outlets above and below the inverter is at least 100

clearance for each of the cooling inlets and outlets above and below the inverter is at least 100
mm.

mm.

Environmental requirements are described in section 1.1

Environmental requirements are described in section 1.1

The  MIDIMASTER  Vector  must  be  secured  to  a  suitable  load-bearing  wall  by  M8  bolts,  washers  and  nuts.

The  MIDIMASTER  Vector  must  be  secured  to  a  suitable  load-bearing  wall  by  M8  bolts,  washers  and  nuts.
Frame size 4, 5 and 6 units need four bolts. Frame size 7 units should be lifted using the two lifting holes and

Frame size 4, 5 and 6 units need four bolts. Frame size 7 units should be lifted using the two lifting holes and
secured by six bolts.

secured by six bolts.

W

W

H

H

D

D

D

D

H

H

H

H

D

D

H

H

D

D

Figure 3.1.1: 

Figure 3.1.1:  MIDIMASTER Vector - Fram

MIDIMASTER Vector - Frame Size 4, 5, 

e Size 4, 5, 6 and 7 

6 and 7 

Summary of Contents for MICROMASTER Vector MMV110

Page 1: ...ION MIDIMASTER MIDIMASTER Vector Vector 25 25 4 4 CONTROLS CONTROLS AND AND BASIC BASIC OPERATION OPERATION 32 32 5 5 OPERATING OPERATING MODES 36 MODES 36 6 6 SYSTEM SYSTEM PARAMETERS PARAMETERS 41 41 7 7 FAULT FAULT AND AND WARNING WARNING CODES 65 CODES 65 8 8 SPECIFICATIONS SPECIFICATIONS 67 67 9 9 SUPPLEMENTARY SUPPLEMENTARY INFORMATION 73 INFORMATION 73 MICROMASTER MICROMASTER Vector Vector ...

Page 2: ...23 3 2 2 2 2 6 6 B Bl lo oc ck k D Di ia ag gr ra am m M MI IC CR RO OM MA AS ST TE ER R V Ve ec ct to or r 2 24 4 3 3 I In ns st ta al ll la at ti io on n M MI ID DI IM MA AS ST TE ER R V Ve ec ct to or r 25 25 3 3 1 1 M Me ec ch ha an ni ic ca al l I In ns st ta al ll la at ti io on n 2 25 5 3 3 2 2 E El le ec ct tr ri ic ca al l I In ns st ta al ll la at ti io on n 2 28 8 3 3 2 2 1 1 P Po ow we...

Page 3: ...7 7 F Fa au ul lt t a an nd d W Wa ar rn ni in ng g C Co od de es s 65 65 7 7 1 1 F Fa au ul lt t C Co od de es s 6 65 5 7 7 2 2 W Wa ar rn ni in ng g C Co od de es s 6 66 6 8 8 S Sp pe ec ci if fi ic ca at ti io on ns s 67 67 9 9 S Su up pp pl le em me en nt ta ar ry y I In nf fo or rm ma at ti io on n 73 73 9 9 1 1 A Ap pp pl li ic ca at ti io on n E Ex xa am mp pl le e 7 73 3 9 9 2 2 U US SS S ...

Page 4: ... the inverter to restart automatically after an input inverter to restart automatically after an input power failure power failure This This equipment equipment is c is capable of apable of providing providing internal internal motor overload protection in accordance with motor overload protection in accordance with UL508C UL508C section section 42 42 Refer Refer to to P074 P074 Moto Moto overload...

Page 5: ...minal current current The The motor motor data data parameters parameters must must be be accurately accurately entered entered P080 P085 and P080 P085 and an an auto auto calibration performed P088 1 calibration performed P088 1 before the motor before the motor is started is started Unstable unpredictable Unstable unpredictable motor operation eg reverse rotation may result if this is not done m...

Page 6: ...rivativ ral Derivative PID e PID control loop control loop function function 15 V 50 mA supply provided for feedback transducer 15 V 50 mA supply provided for feedback transducer Remote control Remote control capability capability via RS485 via RS485 serial li serial link using nk using the USS the USS protocol w protocol with the ith the ability to ability to control up control up to 31 to 31 inv...

Page 7: ...Do not install the water hazards e g Do not install the inverter beneath inverter beneath pipes that are subject to pipes that are subject to condensation Avoid installing condensation Avoid installing the inverter where excessive humidity and the inverter where excessive humidity and condensation may occur condensation may occur Ensure that the inverter s air vents are not obstructed Ensure that ...

Page 8: ...r an r and en d ensur sure th e that a at a good electrical connection is made between the heatsink and the panel removing paint if necessary good electrical connection is made between the heatsink and the panel removing paint if necessary 3 3 Whe Wherev rever po er possi ssible ble use use scr screen eened l ed lead eads for s for con connec nectio tions t ns to the o the con contro trol ci l cir...

Page 9: ...Frame Size B MAINS POWER INPUT MAINS POWER INPUT METAL BACK PLATE METAL BACK PLATE FOOTPRINT FILTER FOOTPRINT FILTER CONTROL CONTROL CABLE CABLE CONTROL CONTROL CABLE CABLE Fix motor and control cable screens Fix motor and control cable screens securely to metal back plate using securely to metal back plate using suitable clips suitable clips EARTH BRAID EARTH BRAID EARTH BRAID EARTH BRAID MAINS P...

Page 10: ...ICROMASTER and MIDIMASTER Vector The MICROMASTER and MIDIMASTER Vector inverters will operate without nuisance tripping with inverters will operate without nuisance tripping with an RCD an RCD also called ELCBs or RCCBs fitted to the input providing also called ELCBs or RCCBs fitted to the input providing A A type type B B RCD RCD is is used used The trip The trip limit limit of of the the RCD RCD...

Page 11: ...h 2 th 2 3 3 years years but but the ste the steps sh ps should be ould be 2 hours 2 hours preparation preparation time 8 time 8 hours hours 1 3 4 1 3 4 Operation Operation with Long with Long Cables Cables Motor cable lengths vary depending on type of cable power rating and voltage rating and in some cases can Motor cable lengths vary depending on type of cable power rating and voltage rating and...

Page 12: ...ing instructions qualified personnel in compliance with the warnings laid down in these operating instructions Take particular note of general and regional installation safety regulations regarding work on Take particular note of general and regional installation safety regulations regarding work on dangerous voltage installations e g VDE as well as the relevant regulations regarding the correct d...

Page 13: ... washers and nuts MICROMASTER Vector inverters must be secured to a suitable vertical surface by bolts washers and nuts Frame size A units need two bolts or can be DIN rail mounted Frame size B and C units require four bolts Frame size A units need two bolts or can be DIN rail mounted Frame size B and C units require four bolts Figure 2 1 1 Figure 2 1 1 MICROMASTER Vector MICROMASTER Vector Frame ...

Page 14: ...Model MMVxxx MMVxxx 1 AC 230V 1 AC 230V Class A Class A Filter Filter MMVxxx 2 MMVxxx 2 1 3 AC 1 3 AC 230V 230V Without Without Filter Filter MMVxxx 3 MMVxxx 3 3 AC 380 3 AC 380 500V 500V Without Without Filter Filter Frame Sizes Frame Sizes all measurements in mm all measurements in mm MMV12 MMV12 MMV25 MMV25 MMV37 MMV37 MMV55 MMV55 MMV75 MMV75 MMV110 MMV110 MMV150 MMV150 MMV220 MMV220 MMV300 MMV...

Page 15: ... L3 3 L2 L2 L1 L1 P PE E P PE E P PE E V V V V U U U U MOTOR MOTOR FUSES FUSES CONTACTOR CONTACTOR FILTER FILTER L L3 3 MICROMASTERVector MICROMASTERVector L L1 1 L L2 2 L3 L3 L L2 2 L L1 1 P PE E P PE E P PE E V V V V U U U U MOTOR MOTOR THREEPHASE THREEPHASE TYPICAL INSTALLATION TYPICAL INSTALLATION SINGLE PHASE SINGLE PHASE Figure 2 2 1 Figure 2 2 1 MICROMASTER Vector Connectors MICROMASTER Vec...

Page 16: ...ng beneath the inverter inverter Frame size C Frame size C use a small bladed screwdriver use a small bladed screwdriver as shown in Figure 2 2 3 as shown in Figure 2 2 3 to release the gland plate and the to release the gland plate and the fan housing allow them both to swing down to hang beneath the inverter fan housing allow them both to swing down to hang beneath the inverter Connect the cable...

Page 17: ... and earth PE as shown in Figure 2 2 1 using a 3 core cable for single phase units or a 4 core cable for and earth PE as shown in Figure 2 2 1 using a 3 core cable for single phase units or a 4 core cable for three phase units For the cross section of each core see section 8 three phase units For the cross section of each core see section 8 4 4 Use a 4 core screened Use a 4 core screened cable to ...

Page 18: ...nd E to release the gland plate and then remove the metal gland plate gland plate and then remove the metal gland plate from the inverter from the inverter 1 1 Insert the blade of a small sc Insert the blade of a small screwdriver into slot A in the rewdriver into slot A in the front of the inverter and press in the direction of the arrow front of the inverter and press in the direction of the arr...

Page 19: ...ully measure and cut the cable cut the cable leads for the leads for the control connections control connections if required Feed the if required Feed the control cable control cable through the correct gland see Figure 2 2 2 and secure the gland to the metal gland plate through the correct gland see Figure 2 2 2 and secure the gland to the metal gland plate 10 10 Carefully feed the power and cont...

Page 20: ...and p d pla late te re rele leas ase t e tab abs s D D C Co on nt tr ro ol l c ca ab bl le e i in np pu ut t E E M Ma ai in ns s c ca ab bl le e i in np pu ut t F F M Mo ot to or r c ca ab bl le e o ou ut tp pu ut t G G B Br ra ak ki in ng r g re es si is st to or r D DC C l li in nk c k ca ab bl le i e in np pu ut t H H J J H H F Fa an n c co on nn ne ec ct to or r J J F Fa an n H Ho ou us si in ...

Page 21: ...for three phase units For able for three phase units For the cross section of each core see section 8 the cross section of each core see section 8 5 5 Use a 4 core Use a 4 core screened cable to screened cable to connect the motor connect the motor 6 6 Carefully measure and cut the cable Carefully measure and cut the cable leads for power connections motor connections leads for power connections m...

Page 22: ... RL1A RL1A NC NC RL1B RL1B NO NO RL1C RL1C COM COM RL2B RL2B NO NO RL2C RL2C COM COM P P P PE E P5V P5V N N 2 23 3 2 24 4 2 25 5 2 26 6 RS485 RS485 for USS protocol for USS protocol Note Note ForPTCmotorthermal ForPTCmotorthermal protection P087 1 protection P087 1 Front Panel Front Panel RS485 D type RS485 D type N N 0 0V V 5V max 250mA 5V max 250mA P P PE case PE case 6 6 1 1 5 5 9 9 Figure 2 2 ...

Page 23: ...ed motors require de rating for continuous operation at low frequencies To ensure that motors are protected against overheating under these conditions it is strongly recommended that a PTC temperature sensor is fitted against overheating under these conditions it is strongly recommended that a PTC temperature sensor is fitted to the motor and connected to the inverter control terminals as shown in...

Page 24: ...3 L L1 N L2 L3 4 4 B B 15 15 26 26 25 25 24 24 23 23 22 22 21 21 20 20 13 13 14 14 5 5 PE PE B DC B DC 1 1 10V 10V 0 0V V O OR R P PE E 16 16 0 10V 0 10V 2 10V 2 10V 0 20mA 0 20mA 4 20mA 4 20mA I I AIN1 AIN1 AIN1 AIN1 PE PE 4 7 k 4 7 kΩ Ω AOUT AOUT AIN2 PID AIN2 PID R RL L2 2 P P N N RS485 RS485 A AD D AIN2 PID AIN2 PID 6 6 7 7 8 8 9 9 12 12 24 24V V 10 10 11 11 O OR R 15V 15V DIN1 DIN1 DIN2 DIN2 ...

Page 25: ...E as well as the relevant regulations regarding the correct on high voltage installations e g VDE as well as the relevant regulations regarding the correct use of tools and personal protective gear use of tools and personal protective gear Mount the inverter vertically to a flat non combustible surface Make sure that the unobstructed Mount the inverter vertically to a flat non combustible surface ...

Page 26: ...th D H1 H1 Depth D Depth D H H H H H1 H1 8 5 mm 8 5 mm Frame Sizes 4 5 and 6 Frame Sizes 4 5 and 6 4 bolts M8 4 bolts M8 4 nuts M8 4 nuts M8 4 washers M8 4 washers M8 W1 W1 W1 W1 W W W W 8 5 mm 8 5 mm 6 bolts M8 6 bolts M8 6 nuts M8 6 nuts M8 6 washers M8 6 washers M8 Frame Size 7 Frame Size 7 Figure 3 1 2 Figure 3 1 2 Mechanical Installa Mechanical Installation Diagram M tion Diagram MIDIMASTER V...

Page 27: ...0 0 x x 2 21 10 0 2 23 35 5 5 53 30 0 6 6 2 27 75 5 x x 6 65 50 0 x x 2 28 85 5 2 23 35 5 6 63 30 0 7 7 4 42 20 0 x x 8 85 50 0 x x 3 31 10 0 3 37 74 4 8 83 30 0 IP20 NEMA 1 with integrated EMC IP20 NEMA 1 with integrated EMC class A filter class A filter W W H H D D W W1 1 H H1 1 4 4 27 275 5 x 7 x 700 00 x x 21 210 0 23 235 5 68 680 0 5 5 2 27 75 5 x x 8 80 00 0 x x 2 21 10 0 2 23 35 5 7 78 80 0...

Page 28: ...tors on the MIDIMASTER Vector are shown in Figure 3 2 1 DC DC DC DC D DC C D DC C W W L L1 1 L L2 2 L L3 3 P PE E P PE E 20 20 19 19 18 18 17 17 16 16 15 15 14 14 13 13 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 L L1 1 L L2 2 W W V V U U L3 L3 V V U U 27 27 26 26 25 25 24 24 23 23 22 22 2 2 3 3 1 1 4 4 6 6 5 5 21 21 FS4 5 units FS4 5 units FS6 units FS6 units FS7 units FS7 units PE PE V...

Page 29: ...nected correctly and the equipment is properly earthed sections 3 2 1 and 3 2 2 Ensure that the leads are connected correctly and the equipment is properly earthed Frame size 4 and 5 Frame size 4 and 5 Tighten up each of the power and motor terminal screws to 1 1 Nm Tighten up each of the power and motor terminal screws to 1 1 Nm Frame size 6 Frame size 6 Tighten up each of the power and motor ter...

Page 30: ... 1 3 14 4 1 15 5 1 19 9 1 16 6 1 17 7 1 18 8 2 20 0 A A1 1O OU UT T A AO OU UT T P PT TC C P PT TC C D DI IN N5 5 D DI IN N6 6 Digital Inputs Digital Inputs 7 5 33V max 5mA 7 5 33V max 5mA Motortemp protectioninput Motortemp protectioninput RL1A RL1A NC NC RL1B RL1B NO NO RL1C RL1C COM COM 2 21 1 2 22 2 RL2B RL2B NO NO RL2C RL2C COM COM N N A A2 2O OU UT T P PE E P5V P5V P P 2 23 3 2 24 4 2 25 5 2...

Reviews: