background image

008483_a_−−_−−  p3

IRM270C Instructions for use

The detector reacts to movements by people:
− the passive infrared section (PIR) detects changes in

the infrared energy which is received;

− the microwave section (MW) detects movements.
Extraordinarily reliable detection is made possible
thanks to the intelligent digital signal processing and
system linkage (Matchtec). Only unambiguous and ver-
ified movement signals in the two partial systems will re-
sult in an alarm signal.

The detector reacts with greatest sensitivity to move-
ments that are diagonal to the active zones (direc-
tions shown by arrows, Fig. 1 and 2).
The detector is designed to achieve optimum re-
sponse coupled with the suppression of false alarms.
Nevertheless, it is recommended that the following
points be observed (Fig. 10):
− Do not direct the zones at sources of heat or cold,

nor at points subject to strong sunlight.

− Direct the zones towards uniform references.

Zones which are directed towards heaters (includ-
ing floor heating equipment) can reduce the proba-
bility of detection of movement.

− If it is impossible to avoid positioning the detector

above heaters, you must keep them at a minimum
distance of 1.50m away!

Installation

The detector is intended for use in inside rooms.

Do not remove the printed circuit board from the de-
tector. There is a danger that it may be damaged!

1.

Open the detector (Fig. 3).

2.

Mount the detector on a stable vertical surface.

− Select the height (h) above the floor according to Fig.

1 or 2.

− Corner mounting and 45

°

 installation (right / left) are

possible without any accessories (see Fig. 4A).

− Detector must be inclined at an angle of 2

°

 when

mounting above 3m in order to detect crawling intru-
ders and to ensure the detection range (see Fig. 4B).

− The cable is introduced through one of the knock-out

points A (see Fig. 5).

3.

Wire the connections as shown in Fig. 7.

4.

For strain relief on the connection cable, pierce the

lug B (Fig. 5) and fix the cable with a cable cleat.

5.

Select the desired settings as shown in the section

on ”Programming”.

6.

Replace the cover, screw it down with the screw pro-

vided (Fig. 3).

Detector breakage/removal monitoring 

Fig. 6

If the detector is forcibly removed from the mounting
surface, a sabotage alarm is triggered.
For this, the detector base must be secured with an
additional screw.

Control inputs 

Fig. 7

Walktest remote control

 Terminal 3

Remote control of the

 walktest indicator

. Use switch

DIP1 to select the polarity of the control signal.

Set/unset remote control

 Terminal 4

Remote control of the 

set/unset 

state. Use switch DIP4

to select the polarity of the control signal.

An open control input is HIGH (internal pull-up); for
control with active HIGH, a resistor (typ. 2k

, max.

47k

/detector) must be switched to 0V.

Programming

You can use switches DIP1 to DIP4 to select the follow-
ing functions:

DIP ON

OFF

 (default)

Function

1

LOW (0V)

HIGH (+12V)

Potential for 

walktest ON

at terminal 3

2

see ”PIR−Detection

PIR−Sensitivity of motion

3

see  PIR−Detection
sensitivity” table

PIR−Sensitivity of motion
detection

4

LOW (0V)

HIGH (+12V)

Potential for 

unset

 at ter-

minal 4

5

see ”MW−Sensitivity

MW−Sensitivity of motion

6

see  MW−Sensitivity
Settings” table

MW−Sensitivity of motion
detection

7

PIR

PIR and MW

Detector system function
for 

disarmed

8

−−

−−

not used

PIR−Detection sensitivity

DIP2 DIP3 Sensitivity /

Range

Application

ON

ON

High values
18m

Stricter detection re-
quirements

OFF OFF

Standard (default)
18m

Residential, offices

ON

OFF

Increased stability
18m

Rooms with low
sources of interference

OFF ON

Harsh environ-
ment
Reduced range.

Rooms with consider-
able interference ef-
fects

Setting note for PIR−Detection sensitivity

If the longest wall in the room is less than 5m, do not
use the «High values» sensitivity setting!

MW−Detection sensitivity

DIP5 DIP6 Sensitivity

Range (approx.)

ON

ON

High

25m

OFF OFF

18m

ON

OFF

12m

OFF ON

Low

6m

Setting note for MW−Detection sensitivity

For adjusting the MW−range start with low sensitivity
(see chapter commissioning).

Detector system function

 DIP7

In the 

disarmed

 mode, the MW-Section is switched off if

DIP7 = ON. In this mode, the detector operates as a
passive infrared detector (PIR).
If the detector is operated with an armed/disarmed line,
we recommend DIP7 = ON (MW-Section OFF when

disarmed

). For 

walktest

, the MW detection system is

switched back on.

LED indications

Control line state

Detector
state

LED LED

Arming,
terminal 4

Walktest,
terminal 3

state

red

yel-
low

Change to 

set

any

Memory reset

Set

any

Memory set

Walktest OFF

Alarm stored

Unset

MW−Detection

Unset

Walktest ON

Self-test at
start-up

Walktest alarm

flashing

lit 
for 2.5s

slow
flashing

on

Memory displays

Set memories are shown in the 

unset 

with

 walktest OFF

state.
The 

alarm memory 

(LED flashes red) shows the result

of the last 

set 

period. This memory is always reset when

the system is next in the 

set

 state.

Self-test

The self-test is carried out whenever the supply voltage
is first applied.
A fault is indicated by the red LED lit constantly (this is
only visible when the walktest is switched on).

Commissioning

1.

Switch on the supply voltage.

During the 

self-test

 and the start-up phase with 

walktest

ON, 

the red LED flashes slowly (for about 20 seconds).

− When the red LED goes out, the detector is ready.
− If the red LED lights continuously, there is a fault in the

detector.

2.

Carry out the walk test, i.e. check the complete moni-

toring area to make sure the alarm triggers:
The microwave part must detect movements through-
out the complete active area 

 yellow LED.

Walk upright across the active area at a rate of about 1
step per second in the direction shown by the arrows
(Fig. 1 or 2) and pause.
The detector must also trigger an alarm if the active
area is crossed near to its edges.

Sealing the detector 

Fig. 3

If sealing of the detector is prescribed, apply an adhe-
sive seal over the gap between the base of the detector
and the cover.

Maintenance

Check the function of the detector regularly (at least
once per year) − carry out a 

walktest

, check for dirt and

inspect the fixture.

Troubleshooting

Detector does not react

− Check whether the mirror is inserted.
− Check the supply voltage and polarity.

No alarm display on the detector

− Check programming, control signals and polarities.

No alarm

− Check the alarm relay.
− Check the alarm line.

Continuous or intermittent alarm

− Check the sensitivity setting.

Switch the detector to walk test, mask the detector win-
dow with a sheet of cardboard and wait 30 seconds:
− If the alarm indication disappears:

− ascertain the sources of alarm in the active area,
− remove the cause of the alarm,
− check the evaluation mode,
− reposition the detector or tilt it through 2

°

.

− If the yellow LED lights up even though there is no

movement:
− MW section is possibly too sensitive, or interference

is coming from outside the detection zone;

− track down possible sources of interference and

eliminate them;

− re-position the detector.

Insufficient range

− Check the mounting height and inclination (Fig. 1 or

2).

− Walk at right angles to the active area!
− Check the IR window for soiling.
− Check the detection sensitivity setting.

Options

Curtain mirror IRS272 

Fig. 2

The IRS272 curtain mirror has overlapping active
zones forming a monitored area to provide secure mon-
itoring against intrusion. At installation heights above
3m, mount the detector with a downward inclination of
2

°

.

Changing the mirror:
Remove the wide-angle mirror from the cover using a
No. 1 screwdriver (Fig. 8) and replace it with an IRS272
curtain mirror.

Use the PIR−sensitivity settings «High values»,
«Standard» or «Increased stability».

Mounting bracket IRUM20, IRUM30 

Fig. 9

The mounting brackets IRUM20 (wall-mounting) and
IRUM30 (ceiling mounting) enable the detector to be ro-
tated through 

±

45

°

 and tilted t10

°

/−15

°

.

The monitored zone can differ from that shown in
Fig. 1 or 2, depending on local conditions and the

setting of the mounting bracket.

Approvals

CE

compliance

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

R&TTE 1999/5/EC

compliance

. . . . . . . . . . . . . . . . . . . . . . . 

C−Tic

compliance

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

It is essential to comply with national approval con-
ditions which relate to the use of the product.

Technical data

Supply voltage

8.0 to 16.0V

DC

 (12V nom.)

. . . . . . . . . . . . 

− max. ripple (0...100Hz)

2.0Vpp

. . . . . . . . . . . . . . . . . . . . . 

− voltage monitoring

alarm at <7.2

±

0.5V

DC

. . . . . . . . . . . 

Current consumption (at 8...16V

DC

):

− quiescent

7.5mA

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

− max. (with LED on)

13mA

. . . . . . . . . . . . . . . . . . . . . . . . . . 

Microwave (MW)

10.525GHz

. . . . . . . . . . . . . . . . . . . . . . . . . 

Alarm output:
− semiconductor relay

opens at alarm / fault

. . . . . . . . . 

− alarm holding time

2...3s

. . . . . . . . . . . . . . . . . . . . . . . . . . . 

− contact load rating

30V

DC

 / 100mA (ohmic load))

. . . 

− series resistance

<35

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Tamper contact

30V

DC

 / 100mA (ohmic load)

. . . . . . . . 

Control inputs

LOW 

1.5V / HIGH 

3.5V

. . . . . . . . . . . . . 

Walking speeds:
− wide angle mirror (standard)

0.2...4.0m/s

. . . . . . . . . . . 

− curtain mirror IRS272 (option)

0.2...4.0m/s

. . . . . . . . . . 

Ambient conditions:
− operating temperature

−20

°

C...+55

°

C

. . . . . . . . . . . . . 

− storage temperature

−20

°

C...+60

°

C

. . . . . . . . . . . . . . . 

− air humidity (EN60721)

<95%rH,

. . . . . . . . . . . . . . . . . . . 

non condensing

− EMC resistance

up to 2GHz 30V/m

. . . . . . . . . . . . . . . . . 

− housing protection EN60529, EN50102 IP41 / IK02

Details for ordering

IRM270C

A5Q00007825

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

IRS272 Curtain mirror (4 pcs)

571 733

. . . . . . . . . . . . . . . 

IRUM20 Mounting bracket, wall

562 247

. . . . . . . . . . . . . 

IRUM30 Mounting bracket, ceiling

562 250

. . . . . . . . . . 

Anti-tamper seal

503 251

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Summary of Contents for Matchtec IRM270C

Page 1: ...gel Specchio grandangolare Espejo gran angular Breedhoekspiegel Miroir grand angle IRS272 PN 571 733 Miroir rideau Specchio a tenda Curtain mirror Vorhang Spiegel Espejo de cortina Gordijnspiegel 4 1 Breedhoekspiegel Miroir grand angle 2 15m 10m 5m 0 5m 0 5m 20m 1m 1m h 2 2m max 3 5m min 2 0m 0 0 9m 25m 30m Wall mounting Wandmontage Montage sur mur Montaggio a muro Montaje en pared Montage op een ...

Page 2: ...of airconditioners Detector breakage removal monitoring Abreißüberwachung Contrôle d arrachement Controllo dello strappo Control de ruptura Afbreekbeveiliging Back tamper contact Abreißkontakt Contact d arrachement Contatto di strappo Contacto anti arranque Afbreekcontact 4 9 TOP Cable knock out Kabeldurchführung Passage de câble Foro per il cavo Orificio para cable Kabelpassage Cable attachment K...

Page 3: ...D Arming terminal 4 Walktest terminal 3 state red yel low Change to set any Memory reset Set any Memory set Walktest OFF Alarm stored Unset MW Detection Unset Walktest ON Self test at start up Walktest alarm flashing lit for 2 5s slow flashing on Memory displays Set memories are shown in the unset with walktest OFF state The alarm memory LED flashes red shows the result of the last set period This...

Page 4: ...onssystem wieder eingeschaltet LED Anzeigen Zustand Steuerleitung Zustand Melder LED LED Scharfschaltung Klemme 4 Gehtest Klemme 3 Melder rot gelb Wechsel auf scharf beliebig Speicher Rücksetzen Scharf beliebig Speicher be reit Gehtest AUS Alarm gespei chert Unscharf MW Detektion Unscharf Gehtest EIN Selbsttest bei Startup Gehtestalarm blinkt leuchtet 2 5s blinkt langsam ein Speicher Anzeigen Ein ...

Page 5: ... l état initial de la mémoire Amorcé Mémoire prête test de déplacement ARRET Alarme mémo riséet Non amorcé Détection HF Non amorcé test de déplacement MARCHE Autotest en cas de démarrage déplacement MARCHE Alarme de test de déplacement 2 5s marche éclaire pendant clignote clignote lentement Affichages de la mémoire Les mémoires sont indiquées dans l état non amorcé avec test de déplacement ARRET L...

Page 6: ...o della memoria Armato qualsiasi Memoria definita walktest OFF Allarme me morizzato Disarmato microonde MW Disarmato walktest ON Autotest di avvio Allarme walktest on si accende per 2 5s lampeggia lentamente lampeggia Visualizzazione della memoria Le memorie predefinite vengono visualizzate mediante il LED nel stato disarmato con test di attraversamento OFF La memoria di allarme LED lampeggia ross...

Page 7: ...walktest OFF Alarma almace nada Desarmado detección MW Desarmado walktest ON Autotest de arranque Alarma de walk test on encendido 2 5s parpadea parpadea lento Visualización de la memoria Las memorias establecidas se muestran en el modo desar mado con prueba de desplazamiento desactivada La memoria de alarma LED parpadeando rojo muestra el resultado del último período armado Esta memoria se reinic...

Page 8: ...ven Geheugen gereed Looptest OFF Alarm opgeslagen Onscherp MW detectie Onscherp Looptest ON Zelftest bij op start Looptestalarm on licht 2 5s op knippert knippert langzaam Geheugen indicaties Gezette geheugens worden in de toestand onscherp te zamen met looptest UIT getoond Het alarmgeheugen LED knippert rood toont het re sultaat van de laatste scherpperiode Met de volgende scherpschakeling wordt ...

Reviews: