Siemens Building Technologies

CM2N4625E / 02.1999

Landis & Staefa Division

7/10

• 

Functional check:

Control signal AC 24 V

–  between wires 1-6 : Actuator turns clockwise.
–  between wires 1-7 : Actuator turns counter clockwise.

Control signal AC 230 V

–  between wires 6-4 : Actuator turns clockwise.
–  between wires 7-4 : Actuator turns counter clockwise.

The actuator remains in its current position if no control signal is applied.

• 

Position indication by measuring the potentiometer resistance while the actuator turns
from 0...90°.

• 

Switch the auxiliary switch contacts "A" and "B" while the actuator reaches the
respective switching positions.

The auxiliary switches are factory set:
Switch A: 

Switching point at 5°

Switch B: 

Switching point at 85°

To change the settings of A and B, use a flat blade screwdriver to turn the switch
adjustment dials to the desired setting.

The angle values are valid only for the actuator position "0°" (clockwise direction).

 

Power supply AC 24V 

for

GIB131.1E
GIB135.1E
GIB136.1E

Operating voltage

Control signal AC 24 V (wires 1-6), clockwise
Control signal AC 24 V (wires 1-7), counter clockwise

Safety extra-low voltage (SELV) or
protection by extra-low voltage (PELV) as per
Protection class
Requirements for external safety insulating transformer (100% duty) to
Feeder protection external
Frequency
Power consumption:  running actuator

holding (economy function)

AC 24 V +

 

20 %

HD 384
III as per EN 60 730
EN 60 742
max. 10 A
50/60 Hz
10VA/10 W
1VA/0.5 W (after > 200 s)

 

Power supply AC 230V 

for

GIB331.1E
GIB335.1E
GIB336.1E

Operating voltage

Control signal AC 230 V (wires 6-4), clockwise
Control signal AC 230 V (Wires 7-4), counter clockwise

Protection class
Feeder protection external
Frequency
Power consumption:  turning actuator

holding (economy function)

AC 230 V +

 

10 %

II as per EN 60 730
max. 10 A
50/60 Hz
13 VA/10 W
6 VA/0.5 W (after > 200 s)

 

Auxiliary switches

 for

GIB135.1E
GIB136.1E
GIB335.1E
GIB336.1E

Contact rating
Life: 

6 A resistive, 2 A inductive
5 A resistive, 1 A inductive
no load

Voltage
Protection class
Voltage proof auxiliary switch to housing
Setting range for switchover contacts
Setting increments
Switching hysteresis
Factory setting:

Switch A
Switch B

6 A resistive, 2 A inductive
10

4

 switchings

5 x 10

4

 switchings

10

6

 switchings

AC 24...230 V
II as per EN 60 730
AC 4 kV
5°...85°


85°

Positioners

 (Potentiometer) for

GIB135.1E
GIB335.1E

Resistance change (wires P1-P2)
Load
maximum sliding contact current
Protection class
Voltage proof potentiometer to housing

0...1000 

< 1 W
< 10 mA
III as per EN 60 730
AC 500 V

Connection cables

Power supply AC 24 V (wires 1, 6, 7) / AC 230 V (wires 4, 6, 7)
Auxiliary switches A and B (wires S1...S6)
Potentiometer (wires P1, P2, P3)

3 x 0.75 mm

2

6 x 075 mm

2

3 x 0.75

 

mm

2

Factory settings for
auxiliary switches A and B
(see "Technical design")

Important

Technical data

Summary of Contents for GIB131.1E

Page 1: ...rollers or ON OFF controls e g outside air dampers flue gas dampers etc The actuator s rotational movement clockwise or counterclockwise depends on the electrical control As soon as the operating voltage AC 24 V or AC 230 V is applied the actuator starts to turn The connected damper can be operated as follows via the respective actuator control Damper opens 0 90 Damper closes 90 0 Damper remains i...

Page 2: ...ious mounting options depending on the direction of rotation and shaft length separate parts such as the shaft adapter with position indicator and other mounting parts are shipped separately with the actuator The actuator comes with 0 9 m long pre wired connection cables The following accessories and spare parts are available for function upgrades of the actuators see data sheet N4699 Accessories ...

Page 3: ...pers You can manually adjust the actuator by pushing the button PUSH The actuator can be fastened to shafts with various diameters and in various shapes square round using just one screw due to the L G patented mounting Insert the shaft adapter from either side into the opening for the shaft adapter depending on the damper shaft length For short shafts the shaft adapter is on the duct side The sha...

Page 4: ...er 4 Connection cable for power supply 5 Connection cable for auxiliary switches 6 Gear train disengagement button 7 8 Adjustment dials for auxiliary switches A and B 9 Position indicator 10 Self centering shaft adapter 11 Locking ring for shaft adapter 12 Adapter for position indicator 13 Mounting bracket 4626Z23 10 11 4626Z25 9 4626Z22 11 12 10 4626Z24 9 Setting and operating elements Arrangemen...

Page 5: ... is within the required tolerance Voltage drops at the feed lines must be included Electric parallel connection of these actuators is possible only via relay if used with types GDB 3 1 GLB 3 1 SQE3 SQE8 SQR3 or SQR8 Mechanical Do not mechanically couple the actuators The quantity of actuators required depends on several torque factors After obtaining the damper torque rating Nm m2 from the manufac...

Page 6: ... the dampers and the exact switching position for switches A and B the actuator can only be adjusted with a mounted shaft adapter and position indicator in accordance with the mounting instructions If necessary you can limit the rotational angle in increments of 5 for the entire span by positioning the shaft adapter in the respective position The mounting sets which are used to change the rotation...

Page 7: ...ower consumption running actuator holding economy function AC 24 V 20 HD 384 III as per EN 60 730 EN 60 742 max 10 A 50 60 Hz 10VA 10 W 1VA 0 5 W after 200 s Power supply AC 230V for GIB331 1E GIB335 1E GIB336 1E Operating voltage Control signal AC 230 V wires 6 4 clockwise Control signal AC 230 V Wires 7 4 counter clockwise Protection class Feeder protection external Frequency Power consumption t...

Page 8: ...onditions Operation Climatic conditions Mounting location Temperature Humidity non condensing IEC 721 3 2 Class 2K2 32 70 C 95 r h Class 2M3 IEC 721 3 3 Class 3K5 inside weather protected 32 55 C 95 r h IP Code Housing type according to EN 60 529 IP 54 Conformity In accordance with the directives set forth by the European Union Electromagnetic compatibility EMC Low voltage directive 89 336 EEC 73 ...

Page 9: ...ormally open contact gray pink Q14 S4 Switch B Input black red Q21 S5 Switch B Normally closed contact black blue Q22 S6 Switch B Normally open contact black pink Q24 Positioner P1 Potentiometer 0 100 P1 P2 white red a P2 Potentiometer pick off white blue b P3 Potentiometer 100 0 P3 P2 white pink c 4626A01 Y1 G G0 SP SN AC 24 V GBB13 1 S2 S3 S5 S6 7 P3 S1 S4 Y 6 P1 P2 Y2 N AC 24 V SELV PELV N Regu...

Page 10: ...a Division min 7 300 73 85 8 m a x 9 5 900 min 100 min 60 min 200 20 10 230 4 2 67 5 3 4626M01 100 27 6 ø 5 7 15 197 max 20 P1 P3 1 7 S1 S6 Taptite M6 x 16 13 1 5 GCA 1 GBB 1 GIB 1 Ø 8 25 6 mm 6 18 mm Dimensions Dimensions in mm 1999 Siemens Building Technologies Ltd ...

Reviews: