background image

Figure 3

Mounting the FTS Telephone Assembly

4.

If no additional FTS telephones are installed, leave the end-of-line resistor on
terminals 3 and 4. If there are additional telephones installed on the selected
zone, place the resistor on the last phone in the zone. (Refer to Figure 2.)
In Canada, remove all EOLs and use EOL P/N 140-0347726 (mount using
Model EL-33).

5.

When wiring for the phone has been completed, replace the plug header on
the rear of the telephone assembly.

TO TZC-8B NEG

1

2

3

4

CONNECTING WARDEN’S

STATIONS (TELEPHONES)

MODELS FTS SERIES†

TO TZC-8B POS

+

_

_

+

_

_

END OF LINE

RESISTOR

10K, 1/4W, 1%

P/N 140-383467

+

†THE WARDEN’S STATION

PHONES MAY BE ANY OF

THE FOLLOWING MODELS:

FTS

FTS-P

FTS-C

FTS-CL

FTS-PCL

+

FTS- HEADER FOR

FIRST PHONE IN ZONE

FTS- HEADER FOR

LAST PHONE IN ZONE

1

2

3

4

Figure 2

FTS Series Wiring

MOUNTING

Mount the FTS-Series telephone assembly in either the FB-300S flush backbox, P/N
500-680587, or the FB-301S surface backbox, P/N 500-624388, as shown in Figure 3
using the two #6-32 screws supplied.

T O P

T O P

#6-32

SCREWS

#6-32

SCREWS

FB-300/-301S

BACKBOX

FB-300/-301S

BACKBOX

FTS

TELEPHONE

ASSEMBLY

FTS

TELEPHONE

ASSEMBLY

Siemens Building Technologies, Inc.

8 Fernwood Road

Florham Park, New Jersey 07932

Siemens Building Technologies, Ltd.

2 Kenview Boulevard

Brampton, Ontario L6T 5E4 CN

P/N 315-099454-2

For CE applications in Cerberus E100 systems refer to

Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).

Siemens Gebäudesicherheit

GmbH & Co. oHG

D-80930 München

Reviews: