Figure 3
Mounting the FTS Telephone Assembly
4.
If no additional FTS telephones are installed, leave the end-of-line resistor on
terminals 3 and 4. If there are additional telephones installed on the selected
zone, place the resistor on the last phone in the zone. (Refer to Figure 2.)
In Canada, remove all EOLs and use EOL P/N 140-0347726 (mount using
Model EL-33).
5.
When wiring for the phone has been completed, replace the plug header on
the rear of the telephone assembly.
TO TZC-8B NEG
1
2
3
4
CONNECTING WARDEN’S
STATIONS (TELEPHONES)
MODELS FTS SERIES†
TO TZC-8B POS
+
_
_
+
_
_
END OF LINE
RESISTOR
10K, 1/4W, 1%
P/N 140-383467
+
†THE WARDEN’S STATION
PHONES MAY BE ANY OF
THE FOLLOWING MODELS:
FTS
FTS-P
FTS-C
FTS-CL
FTS-PCL
+
FTS- HEADER FOR
FIRST PHONE IN ZONE
FTS- HEADER FOR
LAST PHONE IN ZONE
1
2
3
4
Figure 2
FTS Series Wiring
MOUNTING
Mount the FTS-Series telephone assembly in either the FB-300S flush backbox, P/N
500-680587, or the FB-301S surface backbox, P/N 500-624388, as shown in Figure 3
using the two #6-32 screws supplied.
T O P
T O P
#6-32
SCREWS
#6-32
SCREWS
FB-300/-301S
BACKBOX
FB-300/-301S
BACKBOX
FTS
TELEPHONE
ASSEMBLY
FTS
TELEPHONE
ASSEMBLY
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
P/N 315-099454-2
For CE applications in Cerberus E100 systems refer to
Installation Instruction A24205-A334-B844 (English) or A24205-A334-A844 (German).
Siemens Gebäudesicherheit
GmbH & Co. oHG
D-80930 München