Element
Des.
Function
Plugs and terminals
X1
Not used
X3
Plug connection to the PMI & mainboard
X15
Plug-in terminal for supply outputs (output 1 and 2) DC 24 V
X16
Plug-in terminal for supply input 2 (Vsys2) DC 24 V
X17
Plug-in terminal for supply input 1 (Vsys1) DC 24 V
X40
Not used
X400
Plug connection for peripheral data bus
LEDs
H201
Supervision of the fuse for supply output 1
H202
Supervision of the fuse for supply output 2
H203
Supervision of the voltage at the supply input 2 (Vsys2)
H204
Supervision of the voltage at the supply input 1 (Vsys1)
H205…
H207
Not used
Fuses
F201
Fuse for supply output 1
F202
Fuse for supply output 2
F203
Fuse for supply input 1 (Vsys1)
F204
Fuse for supply input 2 (Vsys2)
Switch
S1
Switch for supply supervision of X16 and X17
1.4 Pin assignments
1.4.1 Wiring overview
The supply must be routed redundantly if the network terminal is supplied in a fail-safe
manner via a fire control panel or a voice alarm fire control panel.
Features of the FTI2001 fire terminal board
●
Two separate supply inputs for redundant supply
●
Two supervised supply outputs for devices on the serial RS485 circuit
●
Power limited acc. to NFPA 70 / NEC 760
●
Ground faults detected at <1 kΩ
●
All wiring in accordance of article 760 of NEC or local building code
Fire terminal board FTI2001
Pin assignments