1.6 Adjustment elements
Switch
Function
Position
Meaning
S1-1
Supply input 1 'VSYS1' (X17)
ON
Input 1 is not used (default setting)
OFF
Input 1 is used (supervised)
S1-2
Supply input 2 'VSYS2' (X16)
ON
Input 2 is not used (default setting)
OFF
Input 2 is used (supervised)
1.7 Technical data
Supply input 1
(Plug X17)
Supply input 2
(Plug X16)
Designation
'VSYS +1', 'VSYS -1'
'VSYS +2', 'VSYS -2'
Voltage
DC 24 V
Operating current
Max. 11 mA
Fuse input 1 (F203)
1 Amp Schurter AG, P/N 3404.0116.#
Fuse input 2 (F204)
1 Amp Schurter AG, P/N 3404.0116.#
Supply output
(Plug X15)
Designation
'VSYS 1', 'VSYS 2'; 'GND 1', 'GND 2'
Voltage
DC 24 V
Curent
Max. 1 A per output
Fuses output 1 and 2 (F201, F202)
1 Amp Schurter AG, P/N 3404.0114.#
Supervisory
Power limited, supervised for input 1 and
2 voltage
Connection terminals
Inputs and outputs
●
Design
Spring clips
●
Admissible cable cross-section
12…22 AWG
Fire terminal board FTI2001
Adjustment elements
1
12 | 14
A6V10315040_b_en_--