X400
X3
X17
X16
X15
Input 1
Input 2
Output 2
Output 1
PS 1
PS 2
Internal
Figure 3: Wiring for fire terminal board FTI2001
PS 1
Power supply input (necessary)
PS 2
Power supply input for redundant supply
Output 1 / Output
2
Power supply outputs for peripherals
X3
Connector to X3 on PMI & mainboard
X400
Connection for peripheral data bus
Power supply connections allowed for PS 1 / PS 2
●
Periphery board, FCI2016 / FCI2017: X1001, AUX 1, 2 (+); 3, 4 (-)
●
PAD-3, AUX +/-
●
PAD-4, AUX +/-
●
UL Fire protective, signaling listed, regulated power supply
Power supply inputs, input 1 / input 2
●
All power-limited outputs are supervised in respect of input voltage
●
Input 1 is necessary for power supply
●
Input 2 is for redundant power supply
Power supply outputs, output 1/output 2
●
Supervised and power-limited outputs
●
DC 24 V output voltage
●
Max. current of 1 A per output
Fire terminal board FTI2001
Pin assignments
1
10 | 14
A6V10315040_b_en_--