A6V10456393_enUS_c
Building Technologies Division
2016-06-16
DIP switch & EOL jumper
S601
Dip-Switch for address setting
X209
EOL jumper for setting terminal resistor
X203 / X204
Connection to UFP, power supply and grounding
Dip-switch:
8-digit Dip-switch is used for the FT2009 address setting and baud rate setting. The
first 1-4 digits are for setting FT2009 address, the 7-8 digits are for setting UFP
communication baud rate. The 5 and 6 digits are reserved for future use.
Address
DIP switch
Baud Rate
DIP switch
1
2
3
4
7
8
1
On
Off
Off
Off
9600 bps
Off
Off
2
Off
On
Off
Off
19200 bps
On
Off
3
On
On
Off
Off
38400 bps
Off
On
4
Off
Off
On
Off
57600 bps
On
On
5
On
Off
On
Off
6
Off
On
On
Off
7
On
On
On
Off
8
Off
Off
Off
On
Connect to fire control panel FC901/FC2005, 19200 bps is required.
EOL jumper:
EOL jumper is used for setting terminal resistor of UFP.
Jumper IN
Terminal resistor is connected.
Jump OUT
Terminal resistor is not connected.
S601
X209
X203
X204