2

Siemens Industry, Inc.

A6V10456393_enUS_c

Building Technologies Division

2016-06-16

LEDs & buttons & key switch

LEDs:

No.

Color

Status

Functions

1

Red /
Yellow

On

Red: indicate alarm event or NAC activation event
from the zone.
Yellow: indicate supervisory event from the zone.

2

Yellow On

Indicate trouble event from the zone.

3

Green

On

The LED annunciator power.

4

Yellow On

Indicate trouble event from the entire system.
Also indicate FT2009 communication failure.
(supervised at fire control panel).

5

Yellow On

Indicate ground fault event from the entire system.

6

Red

On

Audibles are active.

7

Yellow On

Audibles are silenced.

8

Yellow Flash

Event waiting to be acknowledged.

Off

All events are acknowledged.

9

Yellow On

The panel can be reset.

Off

The panel is reset.

Buttons:

No.

Button

Functions

10

Audibles On /
Silenced

Silence / Un-silence the NAC’s in the event.

11

Acknowledge  Acknowledge 

events.

12

Reset

Resets the fire control panel to quiescent condition.

13

Lamp Test

Test the LEDs and local buzzer.

Key switch:

 The key switch is used for control of button operation.

 Lock key position

Function

Buttons locked.

Buttons unlocked.

Lamp Test

Reset

Acknowledge

Silenced

Trouble

Ground Fault

Power

FT2009-U1

Audibles On

1
2

3

4

5

6
7

8

9

10

11

12

13

firealarmresources.com

Summary of Contents for FT2009-U1

Page 1: ...V DC power source required from an UL listed recognized for fire use regulated power limited power supply l In total up to 8 UFP type devices connected to a fire control panel l Manually activate deactivate NAC s l Acknowledge and reset events from the entire system l Self test function l Flat elegant housing UFP FT2008 Lamp Test Reset Acknowledge Silenced Trouble Ground Fault Power FT2008 U1 Audi...

Page 2: ...nt from the entire system 6 Red On Audibles are active 7 Yellow On Audibles are silenced 8 Yellow Flash Event waiting to be acknowledged Off All events are acknowledged 9 Yellow On The panel can be reset Off The panel is reset Buttons No Button Functions 10 Audibles On Silenced Silence Un silence the NAC s in the event 11 Acknowledge Acknowledge events 12 Reset Resets the fire control panel to qui...

Page 3: ... are for setting UFP communication baud rate The 5 and 6 digits are reserved for future use Address DIP switch Baud Rate DIP switch 1 2 3 4 7 8 1 On Off Off Off 9600 bps Off Off 2 Off On Off Off 19200 bps On Off 3 On On Off Off 38400 bps Off On 4 Off Off On Off 57600 bps On On 5 On Off On Off 6 Off On On Off 7 On On On Off 8 Off Off Off On Connect to fire control panel FC901 FC2005 19200 bps is re...

Page 4: ...olor Black Red Operating location Indoor dry This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation Details for ordering Type Material No Part No Designation Weight FT2009 U1 S54400 A145 A1 10...

Reviews: