A6V10456393_enUS_c
Building Technologies Division
2016-06-16
LEDs & buttons & key switch
LEDs:
No.
Color
Status
Functions
1
Red /
Yellow
On
Red: indicate alarm event or NAC activation event
from the zone.
Yellow: indicate supervisory event from the zone.
2
Yellow On
Indicate trouble event from the zone.
3
Green
On
The LED annunciator power.
4
Yellow On
Indicate trouble event from the entire system.
Also indicate FT2009 communication failure.
(supervised at fire control panel).
5
Yellow On
Indicate ground fault event from the entire system.
6
Red
On
Audibles are active.
7
Yellow On
Audibles are silenced.
8
Yellow Flash
Event waiting to be acknowledged.
Off
All events are acknowledged.
9
Yellow On
The panel can be reset.
Off
The panel is reset.
Buttons:
No.
Button
Functions
10
Audibles On /
Silenced
Silence / Un-silence the NAC’s in the event.
11
Acknowledge Acknowledge
events.
12
Reset
Resets the fire control panel to quiescent condition.
13
Lamp Test
Test the LEDs and local buzzer.
Key switch:
The key switch is used for control of button operation.
Lock key position
Function
Buttons locked.
Buttons unlocked.
Lamp Test
Reset
Acknowledge
Silenced
Trouble
Ground Fault
Power
FT2009-U1
Audibles On
1
2
3
4
5
6
7
8
9
10
11
12
13