background image

P/N 315-699464-10 

 

SIA / ADEMCO 

SYSTEM TROUBLE CODES 

Trouble Type 

Network Trouble 

DACT General Trouble  

DACT Account 1 

DACT Account 2 

General Trouble 

 
 
 

FCC Requirements - Part 68 

This equipment complies with Part 68 of the Federal Communication Commission (FCC) Rules and Regulations. On 
the bottom is a label that contains, among other information, the FCC Registration Number and Ringer Equivalence 
Number (REN) for this equipment. If requested, this information must be provided to the telephone company. 

FCC Registration Number:  

ABK USA-34988-AL-E 

USOC telephone jack: 

 

RJ31X 

Ringer Equivalence Number (REN): 0.4B 

The REN is useful to determine the quantity of devices which may connect to the telephone line.  Excessive REN’s on 
the telephone line may result in the devices not ringing in response to an incoming call.  In most, but not all areas, the 
sum of the REN’s should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, 
as determined by the total REN’s, contact the telephone company to determine the maximum REN for the calling area. 

If the FS-DACT equipment causes harm to the telephone network, the telephone company will notify you in advance 
that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company 
will notify you of the discontinuance as soon as possible. Also, you will be advised of your right to file a complaint with 
the FCC if you believe it is necessary. 

The telephone company may make changes in its facilities, equipment, operations or procedures that could affect the 
operation of your telephone equipment. If this happens, the telephone company will provide advance notice so that 
you can modify your equipment as required to maintain uninterrupted service. 

If you experience trouble with the FS-DACT Board for repair and/or warranty information please contact an authorized 
Siemens Fire Safety representative. 

If the trouble is causing harm to the telephone network, the telephone company may request you disconnect to 
equipment from the network until the problem is solved. You should not attempt to repair this equipment yourself. This 
equipment contains no customer or user serviceable parts. 

This device may not be used on public coin or party line services. 

Changes or modifications not expressly approved by Siemens Fire Safety could void your authority to operate this 
equipment. 

 

SIA DCS 

*

EVENT CODE IDENTIFIER DESCRIPTIONS 

 

4 Digit Code

 

t u 

Device Address

 

Loop (1-4) 

Address (001-252)

 

 

ADEMCO CONTACT ID 

**

EVENT CODE IDENTIFIER DESCRIPTIONS 

 

 

x y 

Input Group # 

Address (001 – 240) 

 

Summary of Contents for FS-DACT

Page 1: ...TING for FS 250 OR FS 250C Step 1 Installation is to be done by qualified personnel who have thoroughly read and understood this instruction sheet Step 2 Disconnect BATTERY and AC prior to working on equipment Step 3 Mount DACT Board as shown using four spacers to the Main Board NOTE Check to see that the header and connectors are mated properly Step 4 Attach ground wire as shown using the nearest...

Page 2: ... handshake frequency 4 2 1400HZ Sends a 4 digit account number and a 2 digit code up to four rounds at 20 pps with 1400 Hz handshake frequency 4 2 2300HZ Sends a 4 digit account number and a 2 digit code up to four rounds at 20 pps with 2300 Hz handshake frequency COMPATIBLE RECEIVERS FORMATS Receiver Manufacturer Compatible Receivers SIA DCS 8 SIA DCS 20 Ademco Contact ID 3 1 1400HZ 3 1 2300HZ 4 ...

Page 3: ...y Trouble Restore YR 298 3 302 298 7 77 NAC Circuit nn Trouble FT 2nn 1 373 4nn 8 83 NAC Circuit nn Trouble Restore FJ 2nn 3 373 4nn 7 73 NAC Circuit Ground Fault FT 299 1 373 299 8 89 NAC Circuit Ground Fault Restore FJ 299 3 373 299 7 73 FDLC Ground Fault Trouble FT 299 1 373 299 8 83 FDLC Ground Fault Trouble Restore FJ 299 3 373 299 7 73 FDLC Trouble FT 30d 1 373 298 8 83 Phone Line 1 Trouble ...

Page 4: ... advance that temporary discontinuance of service may be required If advance notice is not practical the telephone company will notify you of the discontinuance as soon as possible Also you will be advised of your right to file a complaint with the FCC if you believe it is necessary The telephone company may make changes in its facilities equipment operations or procedures that could affect the op...