Installation Instructions

Model FP2011-U1
6.5 Amp Power Supply Module

P/N 315-050222-2

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Canada, Ltd.
1577 North Service Road East
Oakville, Ontario
L6H 0H6 Canada

INTRODUCTION

The Model FP2011-U1 is a modular power supply that
provides primary regulated 26VDC power for normal
operation. The FP2011-U1 is rated at 6.5A and is filtered
and regulated. Regulation is +/- 0.25V under all load/
line cases.

The module incorporates a 4.0A non-resettable slow-
blow fuse on the primary input and includes a built-in
AC line filter for surge and noise suppression. The
FP2011-U1 mounts in a standard enclosure.

There are no serviceable parts to be maintained.

INSTALLATION

Remove all system power before installa-
tion, first battery then AC. (To power up,
connect the AC first, then the battery.)

The installation kit for the FP2011-U1 includes the
following:

One

FP2011-U1 module

Four

#10 lock nuts

One

4-wire cable

For 240VAC installation, reference the
Jumper Removal section on page 2
before installing the FP2011-U1 module.

Mounting

Mount the enclosure to the wall before mounting the
FP2011-U1 power supply to the enclosure.

1.

Make sure that the dedicated circuit breaker for
the FP2011-U1 is turned off at the mains.

2.

Place the FP2011-U1 housing over the four studs
provided in the enclosure indicated in the system
installation manual. (Refer to Figure 1 for a typical
example.)

3.

Using the lock nuts provided, secure the FP2011-
U1 to the mounting studs of the enclosure.

FP2011-U1

Typical Enclosure

FP2011-U1 Mounting

Studs (4 places)

Figure 1

FP2011-U1 Mounting in Typical Enclosure

Wiring

The FP2011-U1 is designed to operate from a 120 or
240 VAC, 50/60 Hz power source. Use a separate or
dedicated circuit breaker. Wire in accordance with the
authority having jurisdiction and Article 760 of the NEC
NFPA 70 latest edition.

Run the earth ground from a suitable source to the
FP2011-U1. Check local requirements. Conduit is not
an acceptable earth ground conductor.

1.

Connect the AC mains to the 3-position terminal
block on the FP2011-U1 as shown in Figure 2.

Black

(L - Live)

White

(N - Neutral)

Green (G - Earth Ground)