CANopen add-on module
19
SFIDK.PS.023.A2.02
7. SDOs (Service Data Objects)
Batch status
Index
Object name
Description
2181h
Batch status
Sub
Name
Access
Type
PDO
Description
index
mapping
0
No. of Entries
R
U8
No
MAG 6000: 8
MASS 6000: 9
1
Mode
R
U8
No
0: Off
1: On
2
Command
R
U8
No
1: Start
2: Pause
3: Stop
3
Setpoint
R
F32
No
Batch quantity
4
Compensation
R
F32
No
Batch compensation
5
Cycle counter
R
U32
No
Cycle counter value
6
Cycle counterReset
R
U8
No
Dummy read
7
Timeout
R
U32
No
Max. Batch time in seconds
8
Timeout Active
R
U8
No
0: Off
1: On
9
Lead constant
R
F32
No
MASS 6000 only
Error information
Index
Object name
Description
2800h
Error information
Contains information about the most
important error from the flowmeter
Sub
Name
Access
Type
PDO
Description
index
mapping
0
No. of Entries
R
U8
No
1
1
1’st Error
R
U32
No
Please see the flowmeter manual for
detailed information about the error
number
Bit31
..
Bit24
Bit23
Bit22
Bit21
..
Bit0
Number
Category
Timestamp
Error Number
0: Information
Time in minutes since error
1: Warning
ocurred
2: Permanent
3: Fatal