Fig.8 Overview
No. Signification
1
LEDs for the status indication of the in-/output
2
Jumper for the polarity of the monitoring for output 1
3
Connection output 1
4
Port for the connection of the 24V supply for output 1
5
Port for the connection of the 24V supply for output 2
6
Connection output 2
7
Jumper for the polarity of the monitoring for output 2
8
Port for the connection of the FD18-BUS detection line
9
Connection input 1
10
Connection input 2
Jumper
Jumper position
Signification
Output1 is not monitored.
Output1 is monitored.(factory default)
Output2 is not monitored.
Output2 is monitored.(factory default)
If the configurations on the control panel and jumper don't match, this is recognized and an
error message is triggered.
Any other jumper position is not allowed.
LED indicator
For each in-/output, one red LED indicate the status.
LED
Signification
Off
Normal operation, in/output is
monitored.
Flashes every 1 s, 250ms on
Input/output activated
Input 1 LED flashes every 1s, 2...5ms on
Localization mode