background image

5

Building Technologies

A6V10436766_b_en_--

Fire Safety

2014-11-27

LED indicator

For each input/output, one red LED indicates the status.

LED

Signification

Off

Normal operation, in/output is monitored.

Flashes every 1 s, 250ms on

Input/output activated

Input LED flashes every 1s, 2...5ms on

Localization mode

Installation

Fig. 9

Fig. 10

Fig. 11

Fig. 12  Detection line connection

Preparation

1.

Determine type of installation:
–  Installation outside a switching cabinet or a control unit:

use FDCH221 housing (Fig. 10) .

–  Installation directly in a switching cabinet or a control unit:

mount the module on an even surface (Fig. 9).

Damage by water!

In humid or wet environments always use FDCH221 housing!

Mounting FDCH221 housing

1.

Open the housing.

2.

Determine the position of the cable entries in the housing
and break them out.

3.

Mount the housing on an even surface with two screws
(Fig. 10). Distance between holes: 182.0

±

1.0mm.

4.

Insert the cables and fix the cables in the housing.

5.

Insert the seal and fix the lid additionally with four screws
(Fig. 11) (only this way is IP65 protection guaranteed).

The housing lid is transparent. Consider a suitable
installation position to make sure that the LEDs of the
module are visible at any time.

Procedure with installation in the housing

CAUTION

Overheating of the input/output module!

1.

Open the housing.

2.

Place the module in the housing and fix it with two
screws (Fig. 9/10).

3.

Close the housing.

Procedure with installation on an even surface

1.

Place the module on an even surface.

2.

Fix the module with two screws (M4 X15) (Fig. 9).
Distance between holes: 63.5

±

1.0mm

Electric connection

1.

Referring to Fig. 1,3,5,7,12 connect the cables to the
corresponding terminals.

2.

Connect resistor/ diode .The resistors must be
connected at the end of the monitored line.

3.

Fix the cables to the module

CAUTION

Mind the positive and negative polar when connecting the

diodes.

Summary of Contents for FDCIO181-1

Page 1: ...ot activated l Output monitoring configurable on off l Control output for equipment 24 VDC max 2 A l Communication with controller via FD18 BUS detector line l Directly used in dry areas Applicable in dusty and humid areas when installed in FDCH221 housing l Sticker Method easy for commissioning Application Input With the input a status can be monitored the input can be configured by controller or...

Page 2: ...onto J2 Fig 2 Fig 2 Input output module jumper position J2 Fig 3 Connection for normal operation with output line monitored for short circuit and open line Configuration The following configurations are possible through controller or configuration tool l After activating the output remains Steady output Pulse output How long the contact remains active can be configured by controller or configurati...

Page 3: ...put How long the contact remains active can be configured by controller or configuration tools pulse duration l Failsafe behavior when the FD18 BUS detector line is current free or in degraded mode The error behavior defines the position of the output through controller or configuration tools in case of an error Off Output remains in the same position as before the error Activation Output is activ...

Page 4: ...activated in case of an error Deactivation Output is deactivated in case of an error The controller does not monitor external equipment status activated inactivated Structure The module consists of the module carrier the printed circuit board the cover and the protection cover The printed circuit board includes the LEDs The LEDs indicate the states of the inputs outputs The cover of the printed ci...

Page 5: ... surface with two screws Fig 10 Distance between holes 182 0 1 0mm 4 Insert the cables and fix the cables in the housing 5 Insert the seal and fix the lid additionally with four screws Fig 11 only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Procedure with installatio...

Page 6: ...nt 0 51 mA Output Capacity Monitoring resistor Diode 2 A 24 VDC 3 3k Ω 1 4w 1N5404 Input Monitoring resistor 3 3k Ω 680 Ω Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 rel Communication protocol FD18 BUS Load factors 3 Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With FDCH221 housing IP65 Details...