Building Technologies

A6V10436766_b_en_--

Fire Safety

2014-11-27

Configuration

The following configurations are possible by controller or configuration tools :

l

The contact is active, when:

Normal mode: normally open NO closes

Inverted mode: normally closed NC opens

l

After activating the output remains:

Steady output

Pulse output: How long the contact remains active can be configured by controller or
configuration tools (pulse duration).

l

Failsafe behavior when the FD18-BUS detector line is current-free or in degraded mode.
The error behavior defines the position of the output through controller or configuration
tools in case of an error:

Off: Output remains in the same position as before the error

Activation: Output is activated in case of an error

Deactivation: Output is deactivated in case of an error

The controller does not monitor external equipment status (activated/inactivated).

Structure

The module consists of the module carrier, the printed circuit board, the cover and the
protection cover. The printed circuit board includes the LEDs. The LEDs indicate the states of
the inputs/outputs. The cover of the printed circuit board is transparent, so that the state of the
LEDs is visible even when the housing is closed.
To protect the modules from environmental influences, housing FDCH221 is optional.

Fig.8 Overview

Legend

1. Input

     5.   LED indicator

2.  Detection line

     6.   Jumper

       3./ 4.  Output

Jumper

Jumper position

Signification

Output is not monitored.

Output is monitored.(factory default)

If the configurations on the control panel and jumper don't match, this is recognized and an
error message is triggered.

Any other jumper position is not allowed.

Summary of Contents for FDCIO181-1

Page 1: ...ot activated l Output monitoring configurable on off l Control output for equipment 24 VDC max 2 A l Communication with controller via FD18 BUS detector line l Directly used in dry areas Applicable in dusty and humid areas when installed in FDCH221 housing l Sticker Method easy for commissioning Application Input With the input a status can be monitored the input can be configured by controller or...

Page 2: ...onto J2 Fig 2 Fig 2 Input output module jumper position J2 Fig 3 Connection for normal operation with output line monitored for short circuit and open line Configuration The following configurations are possible through controller or configuration tool l After activating the output remains Steady output Pulse output How long the contact remains active can be configured by controller or configurati...

Page 3: ...put How long the contact remains active can be configured by controller or configuration tools pulse duration l Failsafe behavior when the FD18 BUS detector line is current free or in degraded mode The error behavior defines the position of the output through controller or configuration tools in case of an error Off Output remains in the same position as before the error Activation Output is activ...

Page 4: ...activated in case of an error Deactivation Output is deactivated in case of an error The controller does not monitor external equipment status activated inactivated Structure The module consists of the module carrier the printed circuit board the cover and the protection cover The printed circuit board includes the LEDs The LEDs indicate the states of the inputs outputs The cover of the printed ci...

Page 5: ... surface with two screws Fig 10 Distance between holes 182 0 1 0mm 4 Insert the cables and fix the cables in the housing 5 Insert the seal and fix the lid additionally with four screws Fig 11 only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Procedure with installatio...

Page 6: ...nt 0 51 mA Output Capacity Monitoring resistor Diode 2 A 24 VDC 3 3k Ω 1 4w 1N5404 Input Monitoring resistor 3 3k Ω 680 Ω Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 rel Communication protocol FD18 BUS Load factors 3 Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With FDCH221 housing IP65 Details...

Reviews: