background image

A6V10402143_f_en_--

Building Technologies

2018-10-03

Control Products and Systems

Cerberus™ PRO

Zone module, external powered

FDCI723

Zone module, external powered, addressed for detector line C-NET.

  Detector line (collective or conventional 110 series, DS11, SynoLINE300/600)

  LED indicator for detector line status: fault, test, etc.

  Two-wire installation for all cable types

  DC 24 V power supply, external, tested to EN 54-4 (detector lines electrically

isolated)

  Microprocessor-controlled signal processing

  Communication via C-NET (addressed individually)

  Can be used in dry, dusty, and humid areas

  Different mounting options

Summary of Contents for FDCI723

Page 1: ...line collective or conventional 110 series DS11 SynoLINE300 600 LED indicator for detector line status fault test etc Two wire installation for all cable types DC 24 V power supply external tested to EN 54 4 detector lines electrically isolated Microprocessor controlled signal processing Communication via C NET addressed individually Can be used in dry dusty and humid areas Different mounting opti...

Page 2: ... Integrated line separator Easy mounting using snap fastener Can be used in dry areas Housing FDCH221 can be used in dusty and humid environments Use For connecting to collective or conventional fire detectors with safety barrier SB3 for areas at risk of explosion 6 5 2 1 4 3 1 Connections for the C NET detector line 4 Detector line input connections Max 32 detectors per line 2 C NET detector line...

Page 3: ...Overview Type Designation Order no Weight kg FDCI723 Zone module external powered S54322 F6 A1 0 106 Accessories Type Designation Order no Weight kg FDCH221 Housing with cover seal and screws S54312 F3 A1 0 282 Metal cable gland M20 x 1 5 A5Q00004478 0 036 M20 metal counter nut A5Q00004479 0 006 FDCM291 Mounting foot A5Q00003855 0 001 DBZ1190 AB 0 5 2 5 mm2 3 pin connection terminal BPZ 4942340001...

Page 4: ...on U rail TS35 2 Mounting in separate housing FDCH221 accessory 3 Use auxiliary terminals DBZ1190 AB accessory for shielded cables Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable...

Page 5: ... reference diode or EOL22 Ex Operating temperature 20 55 C Storage temperature 30 70 C Air humidity non condensing 95 rel Communication protocol C NET Pluggable connection terminals 0 2 1 5 mm2 Color Input output module rack back box Cover cap housing cover RAL 9010 pure white Transparent matt EN 60529 IEC 60529 protection category Without housing With housing FDCH221 IP30 IP65 Standards EN 54 17 ...

Page 6: ...CI723 90 24 132 102 Housing FDCH221 50 207 119 0786 Siemens Schweiz AG Theilerstrasse 1a CH 6300 Zug Technical data see doc A6V10414910 The declared performance and conformity can be seen in the Declaration of Performance DoP and the EU Declaration of Conformity DoC which is obtainable via the Customer Support center Tel 49 89 9221 8000 or https siemens com bt download 15 FDCI723 Input output devi...