Siemens Industry, Inc
,
A6V10334254_en--_g
Building Technologies Division
5
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLDED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864,
certain programming features or options must be limited to specific values or not used at all as
indicated below.
Program feature or
option
Permitted in UL 864?
(Y/N)
Possible settings
Settings permitted in
UL 864
PERIODIC TEST,
PROGRAMMING
RANGE
Y
1 – 24 Hours
1 – 6 Hours
Digital Communication
format
Y
SIA DCS, Ademco
Contact ID, 3/1, 4/2
SIA DCS, Ademco
Contact ID