Siemens FCA2015-U1 Installation Instruction Download Page 10

 

Siemens Industry, Inc

,  

A6V10334254_en--_g 

Building Technologies Division                                                                                                                                         

 

 

10 

FCA2015-U1 EVENT CODES 

 

Event Type 

SIA DCS 

(8 or 20)

*

 

5

 

Ademco 

Contact ID

*

5

 

3/1 

1400 Hz or 

2300HZ 

4/2 

1400 Hz or 

2300HZ 

Fire Alarm 

FA 

pppp

 

1 110 0

p ppp

 

01 

Fire Alarm Restore (Through Reset) 

FH 

pppp

 

3 110 0

p ppp

 

21 

Smoke Alarm 

FA 

pppp

 

1 111 0p 

ppp

 

01 

Smoke Alarm Restore 

FH 

pppp

 

3 111 0p 

ppp

 

21 

Heat Alarm 

FA 

pppp

 

1 114 0p 

ppp

 

01 

Heat Alarm Restore 

FH 

pppp

 

3 114 0p 

ppp

 

2  

21 

Pull Station Alarm 

FA 

pppp

 

1 115 0p 

ppp

 

01 

Pull Station Alarm Restore 

FH 

pppp

 

3 115 0p 

ppp

 

21 

Waterflow Alarm 

SA 

pppp

 

1 113 0

p ppp

 

02 

Waterflow Alarm Restore 

SH 

pppp

 

3 113 0

p ppp

 

22 

Supervisory 

SS 

pppp

 

1 200

 

0

p ppp

 

66 

Supervisory Restore 

SR 

pppp

 

3 200 0

p ppp

 

76 

AC Trouble 

AT 

1 301 00 000 

80 

AC Trouble Restore 

AR 

3 301 00 000 

70 

Trouble 

FT 

pppp

 

1 373 0

p ppp

 

83 

Trouble Restore 

FJ 

pppp

 

3 373 0

p ppp

 

73 

System Battery Trouble 

YT 

1 302 00 000 

87 

System Battery Trouble Restore 

YR 

3 302 00 000 

77 

Phone Line 1 Trouble 

LT 1 

1 351 00 000 

81 

Phone Line 1 Trouble Restore 

LR 1 

3 351 00 000 

71 

Phone Line 2 Trouble 

LT 2 

1 352 00 000 

82 

Phone Line 2 Trouble Restore 

LR 2 

3 352 00 000 

72 

Data Lost 

RT 0 

1 354 00 000 

88 

Automatic Test (Normal) 

RP 

 1 602 00 000 

30 

Automatic Test (Off Normal) 

RY 

1 608 00 000 

39 

Manual Test  

RX 0 

1 601 00 000 

99 

Test Activation 

FX 

pppp

 

1 611 0

p ppp

 

91 

Gas Alarm 

GA 

pppp

 

1 151 0

p ppp

 

03 

Gas Alarm Restore 

GH 

pppp

 

3 151 0

p ppp

 

23 

Communications Fail 

YC 

1 350 00 000 

84 

System Reset 

OR 0 

1 305 00 000 

79 

Test Begin 

FI 

pppp

 

1 604 0

p ppp

 

90 

Test End 

FK 

pppp

 

3 604 0

p ppp

 

92 

Mass Notification Alarm

4

 

PA 

pppp

 

1 120 0p 

ppp

 

11 

Mass Notification Alarm Restore

4

 

PH 

pppp

 

3 120 0p 

ppp

  

31 

Mass Notification Trouble

4

 

PT 

pppp

 

1 375 0p 

ppp

 

83 

Mass Notification Trouble Restore

4

 

PJ 

pppp

 

3 375 0p 

ppp

  

73 

MNS1

XB 

pppp

 

1 789 0p 

ppp

 

11 

MNS1 Restore

1

 

XC 

pppp

 

3 789 0p 

ppp

 

31 

MNS2

1

 

XN 

pppp

 

1 788 0p 

ppp

 

66 

MNS2 Restore

1

 

XP 

pppp

 

3 788 0p 

ppp

 

76 

MNS Trouble

1

 

XU 

pppp

 

1 787 0p 

ppp

 

83 

MNS Trouble Restore

1

 

XV 

pppp

 

3 787 0p 

ppp

 

73 

Security

3

 

TA 

pppp

 

1 137 0p 

ppp

 

68 

Security Restore

3

 

TH 

pppp

 

3 137 0p 

ppp

 

78 

Emergency

2, 4

  

EB 

pppp

 

1 785 0p 

ppp

 

65 

Emergency Restore

2, 4

 

EC 

pppp

 

3 785 0p 

ppp

 

75 

Building

2

 

ZA 

pppp

 

1 152 0p 

ppp

 

65 

Building Event Restore

2

 

ZH 

pppp

 

3 152 0p 

ppp

 

75 

“Other”

2

 

XY 

pppp

 

1 786 0p 

ppp

 

40 

“Other” Restore

2

 

XZ 

pppp

 

3 786 0p 

ppp

 

50 

*

pppp

 is the dialer group or zone number 

 

Summary of Contents for FCA2015-U1

Page 1: ...Siemens Industry Inc Building Technologies Division FCA2015 U1 Serial Digital Alarm Communicator Transmitter DACT Installation Instruction ...

Page 2: ...ent as well as utilization of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www ...

Page 3: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Page 4: ...ERBERUS PRO PANELS 6 INSTALLATION ON XLS DESIGO FIRE SAFETY MODULAR CERBERUS PRO MODULAR 7 FIRMWARE UPDATE ON XLS DESIGO FIRE SAFETY MODULAR CERBERUS PRO MODULAR SYSTEMS 7 FCA2015 U1 WIRING 7 FCA2015 U1 FORMAT DESCRIPTION 8 COMPATIBLE RECEIVERS FORMATS 8 COMPATIBLE ALARM COMMUNICATORS 8 FCA2015 U1 EVENT CODES 10 FCC Statement 12 ...

Page 5: ... the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited to specific values or not used at all as indicated below Program feature or option Permitted in UL 864 Y N Possible settings Settings permitted in UL 864 PERIODIC TEST PROGRAMMING RANGE Y 1 24 Hours 1 6 Hours Digital Communication format Y SIA DC...

Page 6: ...tep 1 Installation should be performed by qualified personnel who have thoroughly read and understood this instruction sheet Step 2 Disconnect BATTERY and AC on the cabinet prior to working on the equipment Step 3 Mount FCA2015 U1 as shown using the four screws that are supplied Step 4 Attach conduit and run wires as required Wire Size 12 22AWG Step 5 Connect the Serial Communication Cable to the ...

Page 7: ...ld Transfer Module Firmware To Panel in Zeus Select the XDACT firmware file under Firmware File then set the Connection Settings as needed and click Start Transfer to begin the update Transfer Completed will be displayed in Zeus after the firmware update has completed FCA2015 U1 WIRING NOTE The RJ31X provides a convenient connection allowing the DACT to be installed and removed without requiring r...

Page 8: ...digit code up to four rounds at 20 pps with 1400 Hz handshake frequency 4 2 2300HZ Sends a 4 digit account number and a 2 digit code up to four rounds at 20 pps with 2300 Hz handshake frequency COMPATIBLE RECEIVERS FORMATS Receiver Manufacturer Compatible Receivers SIA DCS 8 SIA DCS 20 Ademco Contact ID 3 1 1400HZ 3 1 2300HZ 4 2 1400HZ 4 2 2300HZ Honeywell M8000 SIA DCS 8 SIA20 Ademco Contact ID S...

Page 9: ... shall be within 20 feet and in conduit All compatible Alarm Communicators shall be installed in accordance with their installation instructions A means must be provided for detection of faults on the communicator by the fire alarm panel as described in the installation instructions for the communicator This is typically done by connecting a trouble activated relay on the communicator to an input ...

Page 10: ...e Line 2 Trouble Restore LR 2 3 352 00 000 7 72 Data Lost RT 0 1 354 00 000 8 88 Automatic Test Normal RP 1 602 00 000 9 30 Automatic Test Off Normal RY 1 608 00 000 9 39 Manual Test RX 0 1 601 00 000 9 99 Test Activation FX pppp 1 611 0p ppp 9 91 Gas Alarm GA pppp 1 151 0p ppp 0 03 Gas Alarm Restore GH pppp 3 151 0p ppp 2 23 Communications Fail YC 1 350 00 000 8 84 System Reset OR 0 1 305 00 000 ...

Page 11: ...S and Ademco Contact ID can be used for UL 864 10 th Edition off premises signaling ELECTRICAL RATINGS Standby 24DC Module Current 33 5mA Active 24VDC Module Current 43 5mA INDICATORS LED Function Description H100 OK LED Hardware is functionally good H200 L1 FLT Red LED on Solid Line Connection error while dialing out Line 1 Red LED Flashing DACT Dialing out on Line 1 H201 L2 FLT Red LED on Solid ...

Page 12: ...with the limits for a Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the in...

Reviews: