Siemens Industry, Inc
,
A6V10334254_en--_g
Building Technologies Division
11
1
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular only, if set to either “US/Other” or “Canada”
2
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular only, if set to “Canada”
3
XLS/Desigo Fire Safety Modular/Cerberus PRO Modular only, if set to “US/Other”
4
Desigo FC2025/FC2050, FV2025/FV2050, Cerberus PRO FC922/FC924, FV922/FV924 only
5
Only SIA DCS and Ademco Contact ID can be used for UL 864 10
th
Edition off-premises signaling
ELECTRICAL RATINGS
Standby 24DC Module Current
33.5mA
Active 24VDC Module Current
43.5mA
INDICATORS
LED
Function
Description
H100
“OK LED”
Hardware is functionally good
H200
“L1 FLT”
Red LED on Solid – Line Connection error while dialing out, Line 1, Red LED
Flashing DACT Dialing out on Line 1
H201
“L2 FLT”
Red LED on Solid – Line Connection error while dialing out, Line 2, Red LED
Flashing DACT Dialing out on Line 2
H202
“RX”
DACT receiving information in
H203
“TX”
DACT Transmitting information out
H204
“UP RUN”
Green Flashing DACT has heartbeat