MicroHarmony Cell Sizes 40 - 260A Manual
Communication Protocol
19001467: Version 1.0
11-7
s
11
11.9 Mode 10 Data
11.9.1 Modulator to CCB
Mode 10 is dedicated to collecting diagnostic information from the CCB and is also used for issuing ‘Cell Fault
Reset’ commands by setting bit 2 high (‘1’).
Table 11-9: Mode 10 Modulator to CCB Data
11.9.2 CCB to Modulator
The response data for Mode 10 is shown below where bits 2 through 6 indicate a fault condition when set low (‘0’).
Table 11-10: Mode 10 Data from Power Cell to Modulator
Bit
Description
0
0 -> Mode definition bit
1
1 -> Mode definition bit 1
2
Cell Fault Reset
3
0 (not used)
4
0 (not used)
5
0 (not used)
6
Sync pulse for temperature engine
7
Odd Parity Bit
Bit
Description
0
0 -> Mode definition bit 0
1
1 -> Mode definition bit 1
2
Not Q1 Out of Saturation (OOS) Fault
3
Not Q2 Out of Saturation (OOS) Fault
4
Not Q3 Out of Saturation (OOS) Fault
5
Not Q4 Out of Saturation (OOS) Fault
6
Cell Output Fuse (OK)
7
Odd Parity Bit
Summary of Contents for Eupec
Page 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Page 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Page 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Page 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Page 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Page 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Page 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Page 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Page 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Page 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...