11.6 Cell Data
The following tables define the Perfect Harmony Modulator/CCB communication data bytes where bit 0 is the least
significant bit (LSB). Table A-3 shows the information that flows from the Modulator card to the CCB. Table A-4
shows the CCB response message for each of the 4 data modes. The Operating Mode is controlled by the Harmony
microprocessor where Mode ‘00’ is the default mode. Modes ‘01’, ‘10’, and ‘11’ are used for diagnostic purposes
only. All data sent to the CCB is processed by the Cell Control Gal (U31), therefore the functionality of these ‘Up’
bits are totally dependent on the GAL logic.
Table 11-3: Modulator to CCB Data (‘Up’ Bits)
Table 11-4: CCB to Modulator Data (‘Down’ Bits)
Note that the CCB is responsible for latching all CCB initiated fault conditions so that the Perfect Harmony CPU can
properly determine the cause of any CCB faults when cell diagnostics are performed. These CCB faults must remain
latched until a Cell Fault Reset is received by the CCB (bit 2 of Mode ‘01’ or ‘10’). The parity bit is “stripped off” at
the FOLA before getting to the Modulator cell data registers, and replaced with the OR’ed value of the parity fault
and the link fault (CommFault).
‘Up’ Bits
Mode ‘00’
Mode ‘01’
Mode ‘10’
Mode ‘11’
0
0
1
0
1
1
0
0
1
1
2
Enable Output
Fault Reset
Fault Reset
Test Enable
3
Enable Left Pole
0
0
Device Test A
4
Enable Right Pole
0
0
Device Test B
5
Bypass Request
0
0
Not Test Enable
6
Temperature Sync
Reference
Temperature Sync
Reference
Temperature Sync
Reference
Temperature Sync
Reference
7
Parity
Parity
Parity
Parity
‘Down’ Bits
Mode ‘00’
Mode ‘01’
Mode ‘10’
Mode ‘11’
0
0
1
0
1
1
0
0
1
1
2
Cell Fault
OOS Fault
Q1 OOS OK
Q1 Blocking
3
Low DC Bus Voltage
Not Over Voltage
Fault
Q2 OOS OK
Q2 Blocking
4
Cell Temperature
Feedback Signal
Not Under Voltage
Fault
Q3 OOS OK
Q3 Blocking
5
Control PWR OK
Not Cap Sharing Fault Q4 OOS OK
Q4 Blocking
6
Bypass Acknowledge
CCB Communication
OK
Output Fuse OK
Bypass Option
Available
7
Parity
Parity
Parity
Parity
Summary of Contents for Eupec
Page 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Page 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Page 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Page 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Page 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Page 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Page 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Page 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Page 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Page 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...