Diagnostics mes‐
sage
Channel
error
type
(CET)
Exten‐
ded chan‐
nel error
type
(CET)
Assignment Meaning
Remedy
Redundancy error:
Failure in the partner
module <internal er‐
ror code>
0x0630
0x06D0
Redundant
modules
Errors in the redundancy of
the interface module are sig‐
naled.
The accompanying <internal
error code> value provides in‐
formation for service experts.
Replace the partner interface
module.
Redundancy error:
Faulty power supply
0x0630
0x06D1
Redundant
modules
Problems with the power sup‐
ply.
Check the power supply for
possible errors, e.g. overload,
short-circuit.
Replace the interface module,
if necessary/
Redundancy error:
Incorrect bus adapter
in partner module
0x0630
0x06D2
Redundant
modules
The bus adapter of the redun‐
dancy partner module is not
present or is not supported.
Replace the bus adapter in the
partner module.
Redundancy error:
Redundancy partners
have different hard‐
ware / firmware.
0x0630
0x06D3
Redundant
modules
The redundant modules dif‐
fer in terms of the hardware
or firmware versions.
Make sure that the hardware
or firmware versions of the re‐
dundant modules are identi‐
cal:
• Hardware version:
Replace at least one mod‐
ule.
• Firmware version:
Perform a firmware update.
PROFINET IO
Another source of diagnostic events is the PROFINET basic technology in use. It generates
diagnostics messages containing coding that is already defined in the PROFINET IO Standard -
Application Layer Service Definition V2.2.
The actual diagnostics scope used depends on the configuration and parameter assignment.
You can download the standard if needed on the Internet (
) from the
home page of the PROFIBUS user organization.
A.2
Maintenance events
Maintenance events
A maintenance event is generated each time a maintenance requirement is identified. The MT
LED lights up on the module.
Diagnostic messages
A.2 Maintenance events
IM 155-6 PN HA
46
Equipment Manual, 09/2021, A5E39262148-AE
Summary of Contents for ET 200SP HA
Page 6: ...Security information IM 155 6 PN HA 6 Equipment Manual 09 2021 A5E39262148 AE ...
Page 8: ...Preface IM 155 6 PN HA 8 Equipment Manual 09 2021 A5E39262148 AE ...
Page 24: ...Parameters IM 155 6 PN HA 24 Equipment Manual 09 2021 A5E39262148 AE ...
Page 26: ...Behavior of the device name IM 155 6 PN HA 26 Equipment Manual 09 2021 A5E39262148 AE ...