55 / 84
Siemens
Desigo TRA Engineering, mounting and installation
CM111043en_09
Building Technologies
MS/TP networks
2016-02-22
Examples of recommended cable types
Belden
Type
Capacitance
Non-
halogen
Shield
1)
Tempe-
rature
Pairs
Color
3)
9925
39 pF/m
12 pF/ft
Foil + Braid 80
1.5
Black Red White
8102NH 41 pF/m
12.5 pF/ft
NH
Foil + Braid 80
2
2)
Blue White / White Blue
Orange White / White Orange
1419A
43 pF/m
13.1 pF/ft
Foil
80
2
2)
Blue White / White Blue
Orange White / White Orange
1)
Foil + Braid is recommended for harsh environment (mechanical and
electromagnetic interference, e.g. variable speed drives).
2)
2-pair cable to be used with care because of different color scheme.
The two conductors of the second pair must be wired in parallel to the
Reference terminal to prevent a floating conductor.
3)
Recommended color scheme for wiring.
Observe these rules to prevent communications problems.
3-wire
+
White
–
Black
Reference
Red
Shield
Drain wire (bare)
2 pairs
+
White/blue
–
Blue/White
Reference
2 Orange conductors,
parallel
Shield
Drain wire (bare)