Wiring of power lines
2016-02-22
6.2.2
AC 230 V power line cables
The sizing and fusing of the power lines are oriented to overall load and
local regulations.
Fuse max. T 10 A (protection of the PCB tracks to the load circuits / relays).
Supply cables must be secured with cable restraints.
The AC 230 V installation must guarantee that the voltage is at least 230 V -15%
= 196 V at the location of the room automation station.
Each supply point (room automation station) is either connected separately (star
topology) or looped via the neighboring room automation station.