Desigo TRA Engineering, mounting and installation
CM111043en_09
Building Technologies
Installation box / panel for TRA
2016-02-22
Strain relief of cables is done on the outside of the installation box.
Cable screens for screened/shielded wiring must be installed as close as possible
to the cabinet inlet on its metal structure and connected to the building's ground
system.
The following illustrations display the correct connections for shielded and
unshielded cables to the screen and cable fastening rails.
Use only off-the-shelf screen terminal connections for trouble-free screen/shield
connections.
Attaching cables in the cabinet
1
0
7
6
2
z
0
1
9
I/O module
Support rail
Run screen/shield to the
module, but do not
connect it to the module!
Cable fastening rails
Screen/shield connection
Screen/shield rail
Cable screened/shielded
Cable unscreened/
unshielded
The screen rail cannot be used to relieve cable strain.
Screen/shield connection with screen connection terminals
10
76
2z
0
20
Screen connection terminals
10
7
62
z0
21
Screen/shield rail support rail
10
7
62
z0
2
2
Avoid screen/shield braid.
Attaching cables to the
installation box
Attaching cables in the
cabinet