Siemens Schweiz AG 

 

A6V11937668_en--_b 

Smart Infrastructure 

 

2020-07-10 

 

  

Functions 

Automation station for HVAC and building control systems. 
●  System functions (alarming, scheduling, trending, access protection with individually 

definable user profiles and categories) 

●  Freely programmable (close resemblance to CEN standard 11312). All function blocks, 

available in libraries, can be graphically connected. 

●  Engineering and commissioning with the ABT Site Tool using graphical function charts 
●  BACnet communication, in compliance with the BACnet standard including B-BC profile 

(Rev. 1.15) 

●  Generic object viewer for device local data points via an embedded web-based interface 
●  Wireless connection for engineering and commissioning 
●  Integration of Modbus data points via RTU 
●  Direct connection of field devices 

  

Type summary 

 

Type 

Order number  Description 

PXC4.M16 

S55375-C101 

Compact automation station for BACnet MS/TP 

 

 

  

Inputs/outputs 

 

Total number of inputs/outputs (Onboard) 

16 

Number of universal inputs/outputs (UIO) 

12 

Number of relay outputs (DO) 

Number of inputs/outputs (O TXM) 

40 

Number of Modbus data points RTU 

40 

 

 

 

UIO 

Universal inputs/outputs support the following signal types:  
● 

Passive sensors LG-Ni 1000, 2x LG-Ni1000, Pt 1000 (*75, 385), NTC 10k, NTC 100k  

● 

Resistance sensors 1000 Ohm, 2500 Ohm, 2650 Ohm, 1000...1175 Ohm (for setpoint shift) 

● 

Active sensors DC 0 ... 10 V  

● 

Current measurement analog DC 0...20 mA or 4...20 mA, (inputs U1, U2, U7, U8) 

● 

Binary potential-free contacts for signaling functions  

● 

Counter to 25 Hz (electronic switch to 100 Hz) 

● 

Analog outputs DC 0…10 V 

DO 

Relay outputs for binary controls, changeover contact  
(NO, NC, pulse) 

 

 

  

Equipment combinations 

I/O modules TXM (Series D and later) 

 

Description 

Type 

Data sheet 

Digital input module 8 or 16 I/O points 

TXM1.8D, TXM1.16D 

CM2N8172 

Universal module without / with local operation and LCD 

TXM1.8U, TXM1.8U-ML 

CM2N8173 

Super universal module without / with local operation and LCD 

TXM1.8X, TXM1.8X-ML 

CM2N8174 

Relay module without / with local operation 

TXM1.6R, TXM1.6R-M 

CM2N8175 

Resistance measuring module (for Pt100 4-wire) 

TXM1.8P 

CM2N8176 

Triac module 

TXM1.8T 

CM2N8179 

Digital input and relay module 

TXM1.4D3R 

CM2N8188 

 

 

PXC4 can power TXM extensions modules (for details see planning overview A6V11973797) 

Summary of Contents for Desigo PXC4.M16

Page 1: ...freely programmable using graphical programming interface Communication BACnet MS TP 16 inputs outputs 12 universal inputs outputs 4 relay outputs Extendable to 40 inputs outputs via I O modules TXM Integration of Modbus data points via RTU WLAN interface for engineering and commissioning Operating voltage AC 24 V Mounted on standard rails or on the wall Plug in screw terminal blocks ...

Page 2: ...y outputs DO 4 Number of inputs outputs Onboard TXM 40 Number of Modbus data points RTU 40 UIO Universal inputs outputs support the following signal types Passive sensors LG Ni 1000 2x LG Ni1000 Pt 1000 75 385 NTC 10k NTC 100k Resistance sensors 1000 Ohm 2500 Ohm 2650 Ohm 1000 1175 Ohm for setpoint shift Active sensors DC 0 10 V Current measurement analog DC 0 20 mA or 4 20 mA inputs U1 U2 U7 U8 B...

Page 3: ...itch for bus termination and polarization COM MS TP 12 Slider for mounting on DIN rails 13 Eyelets for cable ties 1 Plastic housing 14 Holes for wall mounting 2 Service button identification in network and WLAN on off 15 Date Series and Serial number 3 LEDs for communication and state 16 QR code for default WLAN access description see Technical data LED displays Activity LED Color Activity Functio...

Page 4: ...al declarations CE declarations etc can be downloaded from the following Internet address https siemens com bt download Notes Safety CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage Observe national provisions and comply with the appropriate safety regulations This equipment is intended only for use in a restri...

Page 5: ...ers or install the device in a lockable cabinet Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Technical data Power supply Operating voltage 24 V AC 24 V 15...

Page 6: ... 1 0 mm2 22 to 18 AWG Cu strand without wire end sleeve 1 x 0 6 mm to 2 5 mm2 22 to 14 AWG or 2 x 0 6 mm to 1 5 mm2 22 to 16 AWG Stripping length 6 7 5 mm 0 24 0 29 in Screwdriver Slot screws screwdriver size 1 Max tightening torque 0 6 Nm 0 44 lb ft BACnet MS TP interface Interface type EIA 485 electrically isolated Baud rate 9600 19200 38400 57600 76800 115200 depending on the configuration Inte...

Page 7: ...LAN client is connected Optionally for cyber security reasons the WLAN can be permanently disabled via configuration Default SSID and WLAN password Scan the QR code It will show something like WIFI S PXC4 M16_0000550 T WPA P 1400052738 Then SSID PXC4 M16_0000550 and password 1400052738 Determine manually Use the information from the Date Series SN block It will show something like Date Series 2019...

Page 8: ...175 Ω 900 1295 Ω 0 1 Ω A fixed value of 1 Ω is calibrated to correct line resistance Voltage measurement analog Type Range over range Resolution AI 0 10 V 0 10 V 1 5 11 5 V 1 mV AI 0 10 V standard 0 100 10 110 0 01 Open connection Negative voltage 1 5 V line failure detection Current measurement analog only inputs U1 U2 U7 U8 Type Range over range Resolution Load AI 4 20 mA 4 20 mA 1 6 22 4 mA 1 µ...

Page 9: ...t Max 3 A resistive at DC 30 V NC contact Max 1 A resistive at DC 30 V Min 10 mA resistive at DC 12 V Switch on current NO contact Max 10 A 1 s NC contact Max 3 A 1 s Response release time 7 ms 3 ms typical Contact life at AC 250 V reference values At 0 3 A resistive NO contact at 3 A resistive NC contact at 2 A resistive Reduction fact at ind load cos phi 0 6 5 x 105 switchings 1 x 105 switchings...

Page 10: ...L approbation US Canada UL916 http ul com database CSA certification C22 2 http csagroup org services industries product listing FCC CFR 47 Part 15 Class B BACnet B BC Environmental compatibility 1 The product environmental declaration 1 contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal 1 Docume...

Page 11: ...lowing two conditions 1 This device may not cause interference and 2 this device must accept any interference received including interference that may cause undesired operation Radio frequency radiation exposure Information for USA and Canada This equipment complies with FCC and IC radiation exposure limits set forth for an uncontrolled environment This equipment should be installed and operated w...

Page 12: ...erface EIA 485 BACnet MS TP 68 69 70 COM Interface EIA 485 Modbus RTU Term on off Switch for bus connection Polar on off Switch for polarization 75 to 86 DOx Relay outputs 11 1 4 Wiring lines for field devices Wiring length max 300 m 1 000 ft CU wire or CU strand Cross section depending on the signal 30 m 100 ft applies for signal types AI NTC10K and AI NTC100K or 80 m 260 ft with shielding ...

Page 13: ... general Resistance transmitter Active sensor powered by the automation station Active sensor with external power Do NOT ground external power ground loops Active sensors 0 20 mA or 4 20 mA 2 wire On U1 U2 U7 U8 only Analog outputs Ux Ux V Ux V V Y1 Y2 Y3 Device with input DC 0 10 V General device with control input DC 0 10 V Powered by the automation station General device with control input DC 0...

Page 14: ...om buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11937668_en _b Edition 2020 07 10 Dimensions All dimensions in mm and inches PXC4 M16 183 7 20 198 7 80 117 41 61 124 4 88 4 1 0 16 70 5 2 78 49 1 91 26 5 1 04 45 1 77 67 2 64 110 4 33 3 0 12 7 0 28 PXC4 M16 with I O modules TXM 198 7 80 64 2 52 64 2 52 90 ...

Reviews: