S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-33
03,352),%86'3DGGUHVVHV
To ensure that all nodes can intercommunicate, you must assign them an address:
•
In the MPI network: an “MPI address“
•
In the PROFIBUS DP network: a “PROFIBUS DP address“
On the PG you can specify individual MPI/PROFIBUS addresses for each one of
the nodes (on some of the PROFIBUS DP slaves this is also possible per selector
switch).
'HIDXOW03,352),%86'3DGGUHVVHV
The table below shows you the factory setting of the MPI/PROFIBUS DP
addresses and the highest default MPI/PROFIBUS DP addresses for the devices.
Table 5-14
MPI/PROFIBUS DP addresses
1RGH
GHYLFH
'HIDXOW
03,352),%86
'3DGGUHVV
'HIDXOWKLJKHVW03,
DGGUHVV
'HIDXOWKLJKHVW
352),%86'3DGGUHVV
PG
0
32
126
OP
1
32
126
CPU
2
32
126
5XOHV$VVLJQLQJ03,352),%86'3DGGUHVVHV
Note the following rules before assigning MPI/PROFIBUS addresses:
•
All MPI/PROFIBUS addresses in a subnet must be unique.
•
The highest MPI/PROFIBUS address must be
≥
of the physical
MPI/PROFIBUS address, and it must be identical for each node. (Exception:
Connecting a PG to multiple nodes; refer to the next Chapter).