$SSHQGL[
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
12-16
A5E00105492-03
&DEOHVIRU
DQGFDEOHVIRU
5XQ
•
Bus signals, shielded
(PROFIBUS)
•
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
•
Analog signals, shielded
•
DC voltage (
≤
60 V),
unshielded
•
Process signals (
≤
25 V),
shielded
•
AC voltage (
≤
25 V),
unshielded
•
Monitors (coaxial cable)
In separate bundles or cable
ducts (no minimum clearance
necessary)
•
DC voltage (> 60 V and
≤
400 V), unshielded
•
AC voltage (> 25 V and
≤
400 V), unshielded
In common bundles or cable
ducts
•
DC voltage (> 60 V and
≤
400 V), unshielded
•
AC voltage (> 25 V and
≤
400 V), unshielded
•
DC and AC voltage (> 400 V),
unshielded
LQVLGHFDELQHWV
In separate bundles or cable
ducts (no minimum clearance
necessary)
RXWVLGHFDELQHWV
On separate cable racks with a
clearance of at least 10 cm
•
Bus signals, shielded
(PROFIBUS)
•
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
•
Analog signals, shielded
•
DC voltage (
≤
60 V),
unshielded
•
Process signals (
≤
25 V),
shielded
•
AC voltage (
≤
25 V),
unshielded
•
Monitors (coaxial cable)
LQVLGHFDELQHWV
In separate bundles or cable
ducts (no minimum clearance
necessary)
RXWVLGHFDELQHWV
On separate cable racks with a
clearance of at least 10 cm
DC and AC voltage (> 400 V),
unshielded
•
DC and AC voltage (> 400 V),
unshielded
In common bundles or cable
ducts
ETHERNET
In common bundles or cable
ducts
ETHERNET
Others
In separate bundles or cable
ducts with a clearance of at least
50 cm