&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-3
+RUL]RQWDODQGYHUWLFDOLQVWDOODWLRQ
You can mount an S7-300 either vertically or horizontally. The following ambient air
temperatures are permitted:
•
Vertical installation: from 0 °C to 40 °C
•
Horizontal installation: from 0 °C to 60 °C.
Always install the CPU and power supply on the left or at the bottom.
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
SIEMENS
SF
BU
SF
DC5V
FRC
E
R
UN
ST
OP
S
IEM
EN
S
CPU
CPU
PS
PS
1
2
3
3
SM SM SM SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM SM
Figure 5-1 Horizontal and vertical installation
7KHGLDJUDPLOOXVWUDWHVXQGHUQXPEHU
Vertical installation of an S7-300
Horizontal installation of an S7-300
Rail
)XUWKHULQIRUPDWLRQ
•
the selection and dimensions of rails (racks) can be found in Chapter
0RGXOH
GLPHQVLRQV
•
connections and interfaces (IMs) are found in Chapter
$UUDQJLQJPRGXOHVRQ
PXOWLSOHUDFNV
•
the most important rules on S7-300 operation are found in the Appendix
*HQHUDOUXOHVDQGUHJXODWLRQVRQ6RSHUDWLRQ