Programming the program blocks
5.4 IF_CONF: SDT for the configuration data of the CP
CP 1243-7 LTE
102
Operating Instructions, 01/2015, C79000-G8976-C381-01
"Telecontrol server"
In STEP 7, the corresponding data is located in the "Partner stations" parameter area.".
This field is only used when the telecontrol server is addressed with a name that can be
resolved by DNS or when the IP address is to stored as a string.
Table 5- 5
IF_CONF_TCS_Name
Parameter
Data type
Initial value
Description
Id
UINT
6
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 266
Mode
UINT
Validity (1, 2) - see above (general parameters)
TcsName
-
-
- reserved -
STRING [254]
Name of the telecontrol server that can be resolved by
DNS or IP address as string
RemotePort
UINT
Port of the telecontrol server
Rank
UINT
Priority of the server [1, 2]
1 = first telecontrol server,
2 = second telecontrol server (second server not relevant)
"SMSC"
In STEP 7, the corresponding data can be found in the parameter area "Mobile wireless
communications settings" > "Services and settings".
Table 5- 6
IF_CONF_SMS_Provider
Parameter
Data type
Initial value
Description
Id
UINT
10
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 28
Mode
UINT
Validity (1, 2) - see above (general parameters)
SMSProvider
STRING [20]
Subscriber number of the SMS center (SMSC) of the
mobile wireless network provider with which the mobile
wireless contract was signed for this station.