9 / 12 

Siemens room unit QAA822 

 

   

 

Building Technologies 

Designing 

The room unit is supplied from the connected controller through 2-
wire interface (low voltage, SELV). 
The room unit must be connected to the Climatix controller by two-
wire twisted pair cable.  It is possible to use unshielded conductors. 

Mounting instructions 

  The device is suitable for semi-flush mounting with a recessed 

installation box.  

  The device must not be mounted into recesses, shelves, behind 

curtains or doors or above or near the direct heat sources.  

  Avoid direct sun and draught. 

  The conduit must be sealed on the device side as an air stream 

along the conduit can affect the sensor readings.  

  The permissible ambient conditions for mounting the device must 

be observed. 

  The mounting instructions are enclosed with the device. 

Installation

 

Local installation regulations must be observed. 
    

 

The equipment is not protected against accidental connection to 
AC 230 V.

 

Commissioning 

After interruption of the connection to the 2-wire interface, the 
communication is re-established only if the room units send a 
query about the controller address.  
For QAA07, the time cycle for querying is: 250 ms 
 

Step 

Function 

Description 

LCD test 

All display segments are displayed for 
approx. 2 seconds 

 

Identification of 
the connected 
controller  

The room unit establishes contact with 
the connected Climatix controller

 

Ready for 
operation 

 

Disposal 

The device contains electrical and electronic components and 
must not be disposed as domestic waste. 
 
The valid local legal regulations are to be observed! 
 

 
 

STOP

Warning

 

Device connection 

 

Summary of Contents for Climatix POL822

Page 1: ......

Page 2: ...oard and a room temperature sensor an LCD panel and key buttons for selection of operating mode temperature set up time setting and fan speed The rear cover includes terminal connections for connection of two wire communication conductors Both covers are made of plastic material The cover removal is described in the Installation manual that forms a part of the package Control buttons and display C...

Page 3: ...4 Operation with the use of power saving function of energy recovery and air mixing The flashing icon indicates the failure of generator energy saving function 15 Failure indication The flashing icon indicates a new failure The lighting icon indicates an extinct failure not confirmed quitted by the operator or a failure that has been quit by the operator but has not extinguished yet Further detail...

Page 4: ...indicated on the display by the combination of the relevant icons 6 7 and 8 In the mode Economy the air conditioning unit is heating or cooling so that the temperature required for this Economy mode is reached This mode is indicated on the display by the icon 7 The default setting for this mode is 18 C The current temperature can be changed temporarily by the Plus or Minus buttons The temperature ...

Page 5: ...chedule by the button Fans in six steps within the speed ranges preset for the modes Economy and Comfort if the configuration parameters enable to control the speed from the room unit Temperatures for the modes Economy and Comfort controlled according to the time schedule cannot be changed from the room unit as they are also controlled according to the time schedule or configuration parameters The...

Page 6: ... temperature C Ven outdoor temperature C VoT temperature of heating water on the return pipe C VoC temperature of the cooling water on the return pipe C Spa temperature of the waste gases of gas heating C Odv temperature of exhaust air C Rek temperature behind the recuperator C Chl temperature behind the cooler C Ohr temperature behind the heater C Vlh air humidity Kval air quality The information...

Page 7: ... exceeding 30s The system time can also be set on the control panel of the Climatic controller or through the web viewer of the computer connected to the Climatix controller in the OS designated switchboard The system time setting is described in the document Detailed instructions for control through HMI Climatix The parameters of the Climatix controller are factory preset so that communication is...

Page 8: ...e is 1 007 Zone address 1 1 X The range is 1 to 15 The preset value is 1 008 Enable the network failure detection Enables or disables the detection of the communication network failure The failure is indicated by a blinking notice NET 009 Automatic assignment of the individual address 0 the room unit uses the defined fixed individual address 1 the room unit generates automatically the individual a...

Page 9: ...itions for mounting the device must be observed The mounting instructions are enclosed with the device Installation Local installation regulations must be observed The equipment is not protected against accidental connection to AC 230 V Commissioning After interruption of the connection to the 2 wire interface the communication is re established only if the room units send a query about the contro...

Page 10: ...e room unit 2 wire interface connection Voltage signal logic 0 5 V Voltage signal logic 1 7 V Maximum number of controllers 8 Baud rate 4 8 kbps Cable connection Connection terminals screw terminals Solid or stranded conductors 0 8 2 5 mm2 Cable type 2 wire twisted pair unshielded Max distance between two units 75 m Max total busbar length 125 m Degree of cover protection Protection according to E...

Page 11: ...ilding Technologies Make yourself familiar with the requirements for CE marking as defined in the EMC directive 2004 108 EC Dimensions See Dimensions Colour Front cover rear cover buttons RAL9003 white Weight Without packaging 0 12 kg ...

Page 12: ...al layout Dimensions units mm Connection of the room unit to the Climatix controller Room unit 1 Room unit 2 Climatix controller Process Bus 2 wire interface power supply device power supply data positive device power supply data negative Negative Positive 3982Z07 3982M01 3982M02 ...

Reviews: