6 / 26
Siemens
HMI-LED
CB1P3946en
Building Technologies
HMI-LED overview
2013-08-19
2
HMI-LED
overview
This section introduces the overview of Climatix HMI-LED.
2.1
Function keys and LED indicators
The function keys and LED indicators of HMI-LED are illustrated as below:
* All the pressing and holding operations in this document should last for more
than 2 seconds (the same below).
Name
Action
Description
Press
- To scroll up the present value list page;
- To increase an input value
Key UP
Press and
hold*
- To enter the present value list page
Press
- To scroll down the present value list page;
- To decrease an input value
Key DOWN
Press and
hold
- To enter the present value list page
Press
- To enter the sub page;
- To get value from the present value list or
parameter list;
-
To confirm the modification of parameter list
or the password input
Key SET
Press and
hold
- To switch to the parameter list page and
alarm history page
Press
- To switch among digit position in parameter
configuration page
Key ESC
Press and
hold
- To exit to upper level menu;
- To exit from the parameter list page;
- To cancel the modification
Key SET+UP
Press and
hold
- To send unit switch ON/OFF command to
controller from the default page
Key SET+DOWN
Press and
hold
- To acknowledge the alarm on the alarm list
page
Key SET+ESC
Press and
hold
- To clear the history alarm records on alarm
history page
LED Indicator
HUMIDITY
% RH light
on
- To indicate the real-time humidity
LED Indicator
TEMPERATURE
°C light on
- To indicate the real-time temperature
Others
No indication
- To indicate the current value is neither
temperature nor humidity