Siemens Cerebrus Pyrotronics SA-11P Installation/Wiring Instructions Download Page 8

Sensing Compartment Cover Installation
a

.

Install the cover gasket (Figure 3, 16) on the housing, if not already installed. Be certain the

alignment holes in the cover gasket are aligned with the guides on the housing.

b.

Install the sensing compartment ionization cover (20) when using DI-B3 or DI-B3H (15)

detectors and the PE-11 cover (17) when using an PE-11 detector (14).

c.

Fasten the cover, using the No. 6 screws (18) provided. Tighten snugly, but not so tightly as

to warp cover and cause air leakage around the edges of the cover.

Sensitivity Testing

Test at least as frequently as required by the 

Installation and Test Requirements of NFPA

72

.

a.

Siemens Building Technologies, Inc. smoke detector sensitivities are  factory set and are

not

 field adjustable. The sensitivity range, as measured with the appropriate sensitivity

meter, is listed on the nameplate label on the wiring compartment cover.

b.

To ensure that the sensitivities are within factory-specified limits, sensitivity testing of the

smoke detectors should be accomplished by qualified service personnel only.

c.

The SA-3I provides access to the detector sensitivity test jack through the sensing compart-

ment cover. Access the test jack by lifting up the hinged lid (Figure 3, 21) and inserting the

plug. For further information on testing the DI-B3 and DI-B3H detectors, refer to the

 TM-I3

Instructions,

 P/N 315-086641.

d.

The PE-11 detector monitors smoke sensitivity automatically and requires no test equip-

ment. A green flash of the detector LED about every seven seconds indicates that the

smoke sensitivity is within it listed limits.

MAINTENANCE

The performance of the air duct detector unit may be adversely affected by dirt or foreign matter

on the sampling tubes or detector. If the air holes in the inlet sampling tube become restricted,

the unit cannot receive a proper air sample, and performance is impaired. It is recommended

that the sampling tubes be checked and cleaned periodically. The detector maintenance program

should consist of periodic cleaning of dust from the detector head by a light brushing of all open

slots and by using a vacuum cleaner. For cleaning of Model PE-11, refer to the Installation

Instructions, P/N 315-094198.
The cleaning and test program is recommended for six month intervals, or more frequently,

if needed, depending on the individual detector environment.

CAUTION:

Under no circumstances is the ionization or photoelectric detector portion

of  the  unit  to  be  disassembled  by  anyone  other  than  an  authorized

Siemens Building Technologies, Inc. Systems Technician. For service,

contact  your  nearest  authorized  Siemens  Building  Technologies,  Inc.

Service Representative.

Periodic Testing

It is recommended that the unit be tested periodically to insure optimum performance. This can be

done  by  removing  the  sealing  plug  from  the  inlet  sampling  tube  on  the  opposite  side

of the duct and blowing smoke directly into the inlet tube. Check that the fire alarm system is

activated.

CAUTION:

If the fire alarm system is connected to a central station or fire department,

or  has  external  devices  such  as  fans,  extinguishers,  etc.,  connected,

notify appropriate personnel and disconnect the external devices until all

tests are completed. After testing, reset the system by using the Reset

key, reconnect the devices and notify the personnel that the system is

again operating.

P/N 315-096274-2

Summary of Contents for Cerebrus Pyrotronics SA-11P

Page 1: ...tellite Use Model PE 11 Operation Voltage and Current 120 VAC 50 60 Hz 32A max Alarm Relay DPDT contacts rated at 125 VAC 24 VDC 3A Resistive Trouble Relay SPDT contacts rated at 125 VAC 24 VDC 2A Resistive Smoke Detector Sensitivity Factory set for air duct application See detector nameplate label Alarm Indicator LED on smoke detector displays steady or flashing red light through air duct cover T...

Page 2: ...rs and positioned so as to operate reliably in case of smoke in any part of the air stream In instances where the filters are capable of removing smoke a detector should be installed both upstream and downstream from the filters The air duct detectors because they use sampling tubes which monitor the full width of an air duct overcome the limitations of spot type smoke and heat detectors in the du...

Page 3: ...3 Figure 2 Recommended Locations in Duct Systems Figure 3 Exploded View ...

Page 4: ...ockwashers 8 e Cut a 12 inch by 12 inch access hole in the duct adjacent to the housing to permit checking and cleaning of the sampling tubes The access hole must be covered and sealed when not in use Sampling Tube Selection To insure accurate air sampling inlet sampling tubes are available in four lengths To select the appropriate length determine the outside width of the duct Select the sampling...

Page 5: ...ements should be taken by qualified personnel in accordance with the PDM 3 Instructions P N 315 085535 ELECTRICAL WIRING TheAir Duct Detector Model SA 3I 11P is interconnected and wired following the wiring diagram in Figure 6 Each model requires a two wire circuit of 18 AWG min thermoplastic fixture wire enclosed in conduit or of 18AWG min limited energy shielded cable without conduit if permitte...

Page 6: ... for Models SA 3I and SA 11P CAUTION Do not use looped wire under terminal 5 of the DB 3S or DB 11 base Break wire run to provide supervision of both connections conduit ensure that it is properly connected to the internal metal ground strap using the proper conduit locking nuts Failure to provide proper grounding may result in fatal electrical shock 7 Connect EOL device 1 3K 1 2W resistor to term...

Page 7: ...to place Installation Removal of PE 11 Detector in Base Adapter To Install Align detector with base and insert detector Rotate detector counterclockwise while gently pressing on it until the detector drops fully into base Then rotate the detector clockwise until it stops and locks in place Insert optional locking screw Order Model LK 11 To Remove Rotate the detector counterclockwise until stop is ...

Page 8: ... limits MAINTENANCE The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector If the air holes in the inlet sampling tube become restricted the unit cannot receive a proper air sample and performance is impaired It is recommended that the sampling tubes be checked and cleaned periodically The detector maintenance program sho...