Siemens Cerebrus Pyrotronics SA-11P Installation/Wiring Instructions Download Page 5

5

Installation of the Sampling Tubes
a.

Before installing the tubes, cut a 7/8-inch hole in the duct wall that is directly opposite the

inlet sampling chamber hole in the detector housing.  This will allow the inlet tube to protrude

through the duct.

b.

Attach brackets (10) to the inlet and outlet air sampling tubes with 3/16 screws (11). 

NOTE:  When attaching brackets, be sure to align tubes properly (See Figure 4).

c.

Install the inlet tube by inserting it in through the air sampling chamber as shown in Figure 3

(3).  Face sampling tube holes into the air stream (Figure 4), and secure to the housing

with 8/32 screws (12).

d.

Install the outlet tube (4)

 

by inserting it into the upper socket of the air sampling chamber with

the scarfed end facing downstream (See Figure 4)

.  

Secure the bracket to the housing with an

8/32 screw.

e.

Make sure no sampling holes extend beyond the ductway, that the stopper remains firmly in

position, and that the duct hole

 

is sealed around the protruding sampling tube.

Air Duct Sampling Tube Pressure Measurement

The 

CERBERUS PYROTRONICS

™ Model PDM-3 Pressure Differential Measuring device

should be used to ensure that the sampling tube pressure differential is within the specified

limits (See

 TECHNICAL DATA). 

 Measurements should be taken by qualified personnel in

accordance with the 

PDM-3 Instructions, 

P/N 315-085535.

ELECTRICAL WIRING

The Air Duct Detector Model SA-3I/-11P is interconnected and wired following the wiring diagram

in Figure 6. Each model requires a two-wire circuit of 18 AWG min thermoplastic fixture wire,

enclosed in conduit, or of 18 AWG min limited energy shielded cable, without conduit, if permitted

by local building codes.

Control of Normally Energized and De-Energized Devices

The Model

 

SA-3I/-11P can be wired for direct relay control of normally energized and de-

energized devices as follows (Refer to Figure 5).

a. Wire normally energized devices (fans, blowers, etc.) to the NC contacts between ter-

minals 10 and 11 or 13 and 14 in order to shut down these devices on alarm.

b. Wire  normally  de-energized  devices  (extinguishing  smoke  removal  fan,  etc.)  to  the

NO  contacts  between  terminals  9  and  10  or  12  and  13  in  order  to  activate  these

devices on alarm.

NOTE:

1. All relay contacts are shown with system in the normal supervisory, no alarm, condition.

WARNING:

If the alarm relay contacts on the control board are being used to control 120 VAC operated equip-

ment, then ensure that earth ground is properly connected to the internal ground strap, using the

proper conduit lock nuts. Failure to provide proper grounding may result in fatal electrical shock.

Figure 5

Connections for Control of Normally Energized

and De-Energized Devices

Summary of Contents for Cerebrus Pyrotronics SA-11P

Page 1: ...tellite Use Model PE 11 Operation Voltage and Current 120 VAC 50 60 Hz 32A max Alarm Relay DPDT contacts rated at 125 VAC 24 VDC 3A Resistive Trouble Relay SPDT contacts rated at 125 VAC 24 VDC 2A Resistive Smoke Detector Sensitivity Factory set for air duct application See detector nameplate label Alarm Indicator LED on smoke detector displays steady or flashing red light through air duct cover T...

Page 2: ...rs and positioned so as to operate reliably in case of smoke in any part of the air stream In instances where the filters are capable of removing smoke a detector should be installed both upstream and downstream from the filters The air duct detectors because they use sampling tubes which monitor the full width of an air duct overcome the limitations of spot type smoke and heat detectors in the du...

Page 3: ...3 Figure 2 Recommended Locations in Duct Systems Figure 3 Exploded View ...

Page 4: ...ockwashers 8 e Cut a 12 inch by 12 inch access hole in the duct adjacent to the housing to permit checking and cleaning of the sampling tubes The access hole must be covered and sealed when not in use Sampling Tube Selection To insure accurate air sampling inlet sampling tubes are available in four lengths To select the appropriate length determine the outside width of the duct Select the sampling...

Page 5: ...ements should be taken by qualified personnel in accordance with the PDM 3 Instructions P N 315 085535 ELECTRICAL WIRING TheAir Duct Detector Model SA 3I 11P is interconnected and wired following the wiring diagram in Figure 6 Each model requires a two wire circuit of 18 AWG min thermoplastic fixture wire enclosed in conduit or of 18AWG min limited energy shielded cable without conduit if permitte...

Page 6: ... for Models SA 3I and SA 11P CAUTION Do not use looped wire under terminal 5 of the DB 3S or DB 11 base Break wire run to provide supervision of both connections conduit ensure that it is properly connected to the internal metal ground strap using the proper conduit locking nuts Failure to provide proper grounding may result in fatal electrical shock 7 Connect EOL device 1 3K 1 2W resistor to term...

Page 7: ...to place Installation Removal of PE 11 Detector in Base Adapter To Install Align detector with base and insert detector Rotate detector counterclockwise while gently pressing on it until the detector drops fully into base Then rotate the detector clockwise until it stops and locks in place Insert optional locking screw Order Model LK 11 To Remove Rotate the detector counterclockwise until stop is ...

Page 8: ... limits MAINTENANCE The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector If the air holes in the inlet sampling tube become restricted the unit cannot receive a proper air sample and performance is impaired It is recommended that the sampling tubes be checked and cleaned periodically The detector maintenance program sho...

Reviews: