6.4.6 Logic control inputs
The PCIO2001-A1 provides 16 logic control inputs on the two connectors 'X7' and
'X8'.
The logic control inputs are used to get information and controls from the
connected components.
● Logic 0 with input voltage <3 V
● Logic 1 with input voltage >7 V
Logic control inputs connector - 'X7'
Pin
Description
Remark
1
I1
-
2
I2
-
3
I3
-
4
I4
-
5
I5
-
6
I6
-
7
I7
-
8
I8
-
9
GND
GND reference voltage
10
10 V
10 V reference voltage
Table 50: PCIO2001-A1 logic control inputs connector - 'X7'
Logic control inputs connector - 'X8'
Pin
Description
Remark
1
I9
-
2
I10
-
3
I11
-
4
I12
-
5
I13
-
6
I14
-
7
I15
-
8
I16
-
9
GND
GND reference voltage
10
10 V
10 V reference voltage
Table 51: PCIO2001-A1 logic control inputs connector - 'X8'