Connect external components
Call station extension PTO2006-A1
7
A6V11899867_en--_a
117 | 122
Configuration with the ID-Switch
The ID-Switch must be set to the correct values to identify the components on the
'PACE-Bus' (RS485). The ID must be unique on one 'PACE-Bus' (RS485).
1
2
3
4
5
6
7
ID
Description
X
X
X
X
X
0
0
-
Master component
X
X
X
X
X
1
0
1
First extension
component
X
X
X
X
X
0
1
2
Second extension
component
X
X
X
X
X
1
1
3
Third extension
component
● 0 = OFF; 1 = ON
● X = undefined; can be OFF or ON
● The extension components are defined with the switches 6 and 7. The valid
address range is from 1 to 3. If the switches 6 and 7 are set to 1 to 3, the
switches 1 to 5 don’t matter.