
Install internal components
System operating unit PT1001-A1
6
66 | 122
A6V11899867_en--_a
6 Install internal components
The internal components are mounted and installed in the Cerberus PACE
Compact cabinet or on the front door.
6.1 System operating unit PT1001-A1
The 'System operating unit' PT1001-A1 is designed to be mounted on a front door
of a Cerberus PACE Compact cabinet.
The provided cables are used to connect the PT1001-A1.
6.1.1 Mounting
The 'System operating unit' PT1001-A1 is designed to be mounted on a front door
of a Cerberus PACE Compact cabinet in place of the mounted blind plate.
Fig. 37: PT1001-A1 unmount front door blind plate
1. Take off the earth connection at the blind plate of the Cerberus PACE Compact
cabinet font door.
2. Unscrew the 8 screws of the blind plate.
3. Remove the blind plate.
4. Insert the PT1001-A1.
5. Use the 8 screws to mount the PT1001-A1.
6. Mount earth connections on the top and bottom of the PT1001-A1 to the
cabinet door.
7. Print and insert inscription stripes.
8. Configure and install the PT1001-A1.
Summary of Contents for Cerberus PACE Compact
Page 12: ......