Document No. 550-139 

Installation Instructions  

October 26, 2016 

Siemens Industry, Inc. 

Page 3 of 6 

4.  Connect the FLN. 

 

5.  Connect the point wiring (see 

Wiring Diagram

s). 

6.  Plug the room temperature sensor cable into the 

RTS port. 

7.  Connect the power trunk. DO NOT apply power 

to the controller without first consulting the 
specialist. This TEC is designed to work with 2-
wire AC power (Neutral and Phase (hot) at 24 
Vac +/-20%. Use of the earth terminal is optional 
and if used it should be connected to the nearest 
earth ground (building steel, conduit or duct work 
(if earthed)).) 

 

 

 

CAUTION 

It is very important that the 

neutral that supplies the TEC 

be earth grounded at the source 

of the 24 Vac power. 
Possible erratic equipment 

operation or damage if neutral 

is left floating. 

The installation is complete. 

 

Wiring Diagrams 

 

 

 

CAUTION 

The controller’s DOs control 24 

Vac loads only. The maximum 

rating is 12 VA for each DO. An 

external interposing relay is 

required for any of the following: 
• VA requirements higher than 

the maximum 
• 110 or 220 Vac requirements 
• DC power requirements 
• Separate transformers used to 

power the load 

(for example part number 540-

147, Terminal Equipment 

Controller Relay Module) 

 

 

 

Summary of Contents for BACnet PTEC Dual Duct 2 AVS

Page 1: ...uctions explain how to field install or replace a Siemens BACnet PTEC Dual Duct 2 AVS Controller Warning Caution Notation WARNING Personal injury loss of life may occur if you do not follow the procedures as specified CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Product Numbers Siemens BACnet PTEC Dual Duct 2 AVS Controller 550 497PA Shipping ...

Page 2: ...or further information see the Wiring Guidelines Manual 125 3002 Room temperature sensor installed optional 24 Vac Class II power available Supply power to the unit is OFF Any application specific hardware or devices installed Air velocity sensors installed in ducts NOTE If the controller is being installed on a box with 1 or more stages of electric heat the 550 809 MOV with pre terminated spade c...

Page 3: ... the nearest earth ground building steel conduit or duct work if earthed CAUTION It is very important that the neutral that supplies the TEC be earth grounded at the source of the 24 Vac power Possible erratic equipment operation or damage if neutral is left floating The installation is complete Wiring Diagrams CAUTION The controller s DOs control 24 Vac loads only The maximum rating is 12 VA for ...

Page 4: ...rements must be followed NOTE When wiring any actuator that uses a 0 to 10V control signal and ties AC neutral to DC common an additional wire must connect the actuator AC neutral to the DC common of the PTEC TEC AO being used to control the actuator 24 Vac Modulating Control Actuator Symbol TEC Connection Function Terminal Connection Standard Color 1 H Supply SP G Red 2 C Neutral SN G0 Black 8 AO...

Page 5: ...o 550 139 Installation Instructions October 26 2016 Siemens Industry Inc Page 5 of 6 Applications 6665 6666 6667 and 6668 with Hot Water Reheat Applications 6665 6666 6667 and 6668 with Electric Auxiliary Reheat ...

Page 6: ...utomation and control fire safety security management and physical security systems The security functions on these products solutions and services are important components of a comprehensive security concept Drafting implementing and managing a comprehensive and up to date security concept customized to individual needs is nevertheless necessary and may result in additional plant or site specific...

Reviews: