Printer interface
90
Building Technologies
008725_h_en_--
Fire Safety & Security Products
06.2011
33 Printer
interface
33.1 Features
Available for station types
CT11, CI11, CC11
Designed for B2Q191, B1Q101 printers, commercially available ISO-LATIN1
printers and EPSON printers
Depending on use, extra hardware needed to adapt levels
Printer B2Q191 can be connected up directly (for installation inside housing)
Printer can be switched on/off individually via the operating unit
Is always assigned to
all
AREAS available in the station used
Individual parameter settings per printer interface
Event memory can only be printed out when the printer is connected to a
CI11
or
CT11
station
33.2 CT11 application variant
I-Bus
E3I020
RS232
C-Bus
CT11
ST2
F20A020
ST1
ST2
B2Q191
24VDC
K2
K3
or
(9...36VDC)
max.1000m
AlgoPilot B3Q...
in cabinet H26/H28
F20A020
ST2
to printer
E3I020
Z1B020
B3Q...
AlgoPilot B3Q...
I-Bus
B2Q191
ST2
F20A410
A3
C-Bus
max. 1m
24VDC
K2
(TTL)
CT11
Condition:
–
B2Q191 printer is in the same housing as the AlgoPilot B3Q… operat-
ing unit or in a neighboring housing
–
With this application, the earth connection of the 'K3-5' terminal of
K3L080 must be routed to the housing, otherwise ground fault is pro-
duced (see document 001260)
F20A410
in cabinet H26/H28
B2Q191
B3Q...