Line plug-in modules
69
Building Technologies
008725_h_en_--
Fire Safety & Security Products
06.2011
26.6 'MS9i addressing' detector line
The E3M060 allows existing system parts to be integrated with detectors of the
MS9i/MS7i series
Number of elements (addresses) per line: Max. 50, but depends on element
type
1)
1 Loop line
Addressing bus MS9i
max. 50 addresses / 50
E3M060
DJ1192
F716i
R716i
R970
F910
R936
R970
AT50Mi
ATAN50Mi
max. 20 detectors
MS716 collective
MS9 collective
DS11 collective
D2401
F930
R930
E90Mi
E90Mi
E90Ci
BFST
max. 4 detectors
24VDC
K5M010
MS716 collective
MS9 collective
DS11 collective
D2401
Z9..Mi
Parallel detectors (slaves)
1)
DC1192
Ex
SB3
24VDC
DO1101-Ex
DT1101-Ex
2)
MS716i
MS9
DF1101-Ex
E90Mi
Control output for 1 external response indicator in each addressable detector base
Z9..Si
Room 104
Room 102
Room 101
Room 103
fixed allocation (output active as
soon as the internal LED is flashing)
False
ceiling
ZONE 5
ZONE 7
ZONE 9
co
llec
tiv
e
1) For details, see document 825
2) For details, see document 1204