KNX Group Objects
Technical data
Power supply
Operating voltage
G..B111.9E/KN
AC 24 V ± 20% (SELV) or
AC 24 V class 2 (US)
Frequency
50/60 Hz
Power consumption
at 50 Hz
Actuator
holds
1 VA / 0.5 W
Actuator
rotates
3 VA / 2.5 W
Function data
Positioning time for
nominal rotation angle
G..B111.9E/..
150 s (50 Hz)
120 s (60 Hz)
Nominal torque
GDB..
5 Nm
Maximum torque
GDB..
< 7 Nm
Nominal / maximum
rotation angle
90° / 95° ± 2°
Direction of rotation
Adjustable over bus (operating mode
“position control”)
Clockwise (CW) /
Counter-clockwise (CCW)
Connection cables
Cable length
0.9 m
Power supply
Number of cores and cross-sectional area 2 x 0.75 mm
2
Communication
Number of cores and cross-sectional area 2 x 0.75 mm
2
Nr.
Name in ETS
Object
function
Flags
Data point type KNX
Range
C
R
W
T
U
ID
DPT_Name
Format
Unit
1
Fault information
Transmit 1 1 0 1 0 219.001 _AlarmInfo
6
Byte ---
[0...255 ] = Log Nr.
[0...2] = Alarm priority
[0...14] = Application area
[0...4] = Error class
[0...7] = Attributes
[0...7] = Alarm status
2
Fault state
Transmit 1 1 0 1 0 1.005
_Alarm
1 bit
---
0 = No alarm
1 = Alarm
3
Fault transmission
Receive 1 0 1 0 1 1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
4
Setpoint position /
Setpoint pos. heating
1)
Receive 1 1 1 0 1 5.001
_Scaling
1
Byte %
0..100%
5
Actual position /
Actual position heating
1)
Transmit
1 1 0 1 0 5.001
_Scaling
1
Byte %
0..100%
6
Setpoint pos. cooling
1)
Receive 1 1 1 0 1 5.001
_Scaling
1
Byte %
0..100%
7
Actual position cooling
1)
Transmit
1 1 0 1 0 5.001
_Scaling
1
Byte %
0..100%
8
Fault
Transmit
1 1 0 1 0 1.005
_Alarm
1 bit
---
0 = No alarm
1 = Alarm
9
Override position 1
Receive
1 1 1 0 1 1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
10 Override position 2
Receive
1 1 1 0 1 1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
1)
For operating mode “heating / cooling control”