background image

23

SICAM AI Unit 7XV5674, Product Information
E50417-B1150-C492-A1, Edition 09.2012

The conductor cross-section for the 20-mA input 

terminals (T) and (Q) amounts to:

‰

0.2 (AWG 24) to 1.5 mm² (AWG 16), direct connec-

tion of stranded wires without bootlace ferrule is not 

recommended.

Wire stripping length

10 mm (0.39 inch)

Material

Cu / E-Cu

RS485 interface (J) on the terminal side of 

7XV5674-0KK30-xAA1:

RS485 cable with the plug connector D-sub socket 

9-pin

820-nm optical interface (J) on the terminal side of 

7XV5674-0KK40-xAA1:

FO cable fitted with ST connector

Ethernet interface (Z) on the top side:

Ethernet patch cable with RJ45 plug connector or

Y cable if an Ethernet switch is used

DANGER

Danger due to high voltages

Non-observance will lead to death or serious injury.

‰

The grounding on the SICAM AI Unit 7XV5674 

always has to be connected to the protective conduc-

tor terminal 

 (terminal block H).

‰

Do not look into the laser beam, not even with optical 

devices!

Summary of Contents for 7XV5674

Page 1: ...E50417 B1150 C492 A1 SICAM AI Unit Erfassungsgerät mit 20 mA Eingängen 7XV5674 Produktinformation ...

Page 2: ...äglichkeit EMV Richtlinie 2004 108 EG und betreffend elektrische Betriebsmittel zur Verwendung innerhalb bestimmter Spannungsgrenzen Niederspannungsrichtlinie 2006 95 EG Diese Konformität ist das Ergebnis einer Prüfung die durch die Siemens AG gemäß den Richtlinien in Übereinstimmung mit den Fachgrundnormen EN 61000 6 2 und EN 61000 6 4 für die EMV Richtlinie und der Norm EN 61010 1 für die Nieder...

Page 3: ...rer Sicherheit 6 4 Verwendete Symbole 9 5 Bestellinformationen 10 6 Anwendung 11 7 Aufbau 13 8 Montage und Inbetriebnahme 15 9 Anschlussart 20 10 Gemessene und berechnete Größen 21 11 Schnittstellen 22 12 Abgleich 26 13 Batterieaustausch 27 14 LED Meldungen 30 15 Fehlersuche und Instandsetzung 34 16 Lagerung und Transport 35 17 Technische Daten Auswahl 36 ...

Page 4: ...iemens AG keine Haftung für Mängel und Schäden die durch die Nut zung der hierin enthaltenen Informationen entstehen Diese Inhalte werden weder Teil eines Vertrags oder einer Geschäftsbeziehung noch ändern sie diese ab Alle Verpflichtungen der Siemens AG gehen aus den entsprechenden vertraglichen Vereinbarungen hervor Die Siemens AG behält sich das Recht vor dieses Dokument von Zeit zu Zeit zu änd...

Page 5: ...trotechnisch qualifiziertes Personal das speziell ausgebildet ist oder einschlägiges Wissen auf dem Gebiet der Automatisierungstechnik besitzt Die Kenntnis und das technisch einwandfreie Umset zen der in dieser Produktinformation enthaltenen Sicherheitshinweise und Warnungen sind Vorausset zung für gefahrlose Installation und Inbetriebnahme sowie für Sicherheit bei Betrieb und Instandhaltung der b...

Page 6: ...fordern Bei Fragen zum Gerät wenden Sie sich an den Sie mens Vertriebspartner in Ihrer Region Unser Energy Customer Support Center unterstützt Sie rund um die Uhr Tel 49 1805 24 8437 Fax 49 1805 24 2471 Internet http www siprotec de E Mail support ic siemens com 3 Hinweise zu Ihrer Sicherheit Dieses Handbuch stellt kein vollständiges Verzeichnis aller für einen Betrieb des Betriebsmittels Baugrupp...

Page 7: ...e alle Hinweise um Tod oder schwere Verletzungen zu vermeiden VORSICHT Vorsicht bedeutet dass mittelschwere oder leichte Verletzungen eintreten können wenn die angegebe nen Maßnahmen nicht getroffen werden Beachten Sie alle Hinweise um mittelschwere oder leichte Verletzungen zu vermeiden ACHTUNG Achtung bedeutet dass Sachschäden entstehen kön nen wenn die angegebenen Maßnahmen nicht getrof fen wer...

Page 8: ...g und der technischen Beschreibung vorge sehenen Einsatzfälle und nur in Verbindung mit von Siemens empfohlenen bzw zugelassenen Fremdge räten und komponenten verwendet werden Wird das Gerät nicht gemäß dieser Produktinformation benutzt ist der vorgesehene Schutz beeinträchtigt Der einwandfreie und sichere Betrieb des Produktes setzt sachgemäßen Transport sachgemäße Lage rung Aufstellung und Monta...

Page 9: ...ser Produktinformation und im Gerätehand buch genannten Grenzwerte dürfen nicht überschrit ten werden dies ist auch bei Prüfung und Inbetriebnahme zu beachten 4 Verwendete Symbole Tabelle 4 1 Verwendete Symbole Nr Symbol Beschreibung 1 Gleichstrom IEC 60417 5031 2 Wechselstrom IEC 60417 5032 3 Gleichstrom und Wechselstrom IEC 60417 5033 4 Erdungsanschluss IEC 60417 5017 5 Schutzleiterklemme IEC 60...

Page 10: ...rotokoll Optisch 820 nm ST Verbindungsstecker 4 Serieller Modbus RTU und SIPROTEC 20 mA Protokoll 0 K Ethernet Schnittstelle für Web Server und Modbus TCP 1 Ethernet Schnittstelle für Web Server IEC 61850 und Modbus TCP 2 Serielle Schnittstelle und Kommunikationsprotokoll Ethernet Schnittstelle und Kommunikationsprotokoll Zwölf 20 mA Eingänge Hutschienengerät ohne Display IP20 Abmessungen 96 mm x ...

Page 11: ...eldsignalen einsetzen Schutztechnik SCADA DMS EMS Systeme GIS Gasisolierte Schaltanlagen Gasdruck Überwachung Andere industrielle Prozesse Hierbei ist es z B möglich die 4 mA bis 20 mA Signa le der Wandler Überwachung von Leistung Tempera turen Druck Position für weitere Verarbeitung z B Visualisierung oder Verbindung zu anderen automati sierten Prozessen über das Standardprotokoll zu über mitteln...

Page 12: ...hnittstelle als RS485 oder optische Schnittstelle unterstützt folgende Funktionen Übertragung von Messdaten Übertragung von Meldungen Zeitsynchronisation mit Feldbus Zur Kommunikation kann je nach Geräteausführung das Kommunikationsprotokoll Modbus RTU oder SIPROTEC RTU 20 mA genutzt werden Mit dem integrierten Web Server erfolgt die Parame trierung mittels HTML Seiten unter Verwendung eines Web B...

Page 13: ...e befinden sich der Ethernet Steckverbinder RJ45 mit 2 LEDs und 4 weitere LEDs Am Batteriefachdeckel befinden sich ein Beschriftungs feld für die parametrierbaren LEDs H1 H2 ERROR und ein Batteriesymbol mit der Darstellung der Batteriepo larität Ebenso ist auf der Oberseite das Typenschild aufgeklebt das u a die wichtigsten Nenndaten des Gerätes enthält Unter dem abnehmbaren Batterie fachdeckel be...

Page 14: ...7 2 Hutschienenseite der SICAM AI Unit 7XV5674 Auf der Hutschienenseite ist mittig die Hutschienenhal terung befestigt Außerdem befindet sich im rechten unteren Teil der IP Addr Tastschalter mit dem per Knopfdruck 3 s bei Bedarf die werkseitig vorgege bene Default IP Adresse eingestellt werden kann Diese und die Standard Subnetz Maske sind auf der Seitenwand siehe Bild 7 2 ablesbar Hutschienen hal...

Page 15: ...chnitte von max 1 5 mm AWG 16 bis 2 5 mm AWG 14 ausgelegt Die Anschlussklemmen der 20 mA Eingänge T und Q sind für Leitungsquerschnitte von max 0 2 mm AWG 24 bis 1 5 mm AWG 16 ausgelegt Das Gerät darf während des Betriebes keiner Kon densation ausgesetzt werden Das Gerät ist so zu platzieren dass es keiner direk ten Sonneneinstrahlung und keinem starken Tempe raturwechsel ausgesetzt ist GEFAHR Gef...

Page 16: ...Sie die Entriegelung am Hutschienen Clip nach unten und halten Sie die Entriegelung in dieser Position fest 2 Schieben Sie das Gerät mit der Führung des Hut schienen Clips auf eine Seite der Hutschiene 3 Schieben Sie das Gerät auf der Hutschiene an die gewünschte Position 4 Lassen Sie die Entriegelung los Das Gerät ist nun auf der Hutschiene fixiert Entriegelung Zugrichtung Hutschienen Clip Führun...

Page 17: ...nur von elektrotechnisch qualifizier tem Personal siehe Vorwort vorgenommen werden das mit den Sicherheitsbestimmungen und Vorsichts maßnahmen vertraut ist und diese befolgt Die Arbeiten dürfen Sie niemals beim Vorhandensein gefährlicher Spannungen durchführen Führen Sie die Spannungsfreischaltung durch Trennvorrichtung Eine geeignete Trennvorrichtung ist vorzuschalten um das Gerät strom und spann...

Page 18: ...4 Inbetriebnahme Bevor Sie die Versorgungsspannung einschalten prü fen Sie ob die Betriebsdaten mit den Nenndaten auf dem Typenschild und den technischen Daten gemäß Kapitel 17 übereinstimmen Dies betrifft insbesondere die Versorgungsspannung UH und die Maximalwerte von Strom und Spannung des Gerätes Nach einer Betriebsdauer von ca 15 min hält das Gerät die in den technischen Daten angegebenen Tol...

Page 19: ...2 Geräteoberseite 2 Entnehmen Sie aus der Batteriefassung die ver packte Batterie 3 Entfernen Sie die Kunststofffolie von der Batterie 4 Setzen Sie die Batterie unter Beachtung der auf der Geräteoberseite aufgedruckten Polarität in die Bat teriefassung ein 5 Schließen Sie den Batteriefachdeckel Batteriefach Polaritäts Batterie Typenschild angabe der deckel HINWEIS Der Batterieaustausch ist im Kapi...

Page 20: ...1150 C492 A1 Ausgabestand 09 2012 8 5 Parametrierung 9 Anschlussart HINWEIS Die Parametrierung ist im Gerätehandbuch Bestell nummer E50417 G1100 C492 beschrieben HINWEIS Die Anschlussart ist im Gerätehandbuch Bestell nummer E50417 G1100 C492 beschrieben ...

Page 21: ...elwertfenster beginnt immer zu vollen 10s 2 Das Mittelwertfenster beginnt immer zur vollen 1min 3 Das Mittelwertfenster beginnt immer zur vollen 1h 4 Das Mittelwertfenster beginnt immer um 0 Uhr Gerä tezeit Messgröße Messpfad Messbereich Toleranz grenzen 1 Gleichstrom IDC Kanal 1 bis 12 aktuelle Messung 0 mA bis 20 mA 4 mA bis 20 mA 0 2 Messgröße Berechnete Größen Messbereich Gleichstrom IDC Kanal...

Page 22: ...ungsspannung H beträgt 1 5 mm AWG 16 bis 2 5 mm AWG 14 ohne Aderendhülse 1 5 mm AWG 16 mit Aderendhülse Anzugsmoment 0 4 Nm bis 0 5 Nm SICAM AI Unit mit DC Eingängen und RS485 Schnittstelle D Sub Buchse SICAM AI Unit mit DC Eingängen und optische Schnittstelle ST Verbindungsstecker HINWEIS Bei der Lieferung des Gerätes ist die Steckerleiste Phoenix FMC 1 5 9 ST 3 81 für Anschlüsse T und Q beigeste...

Page 23: ...mit dem Steckverbinder D Sub Buchse 9 polig 820 nm optische Schnittstelle J auf der Klemmenseite des 7XV5674 0KK40 xAA1 LWL Kabel mit ST Verbindungsstecker konfektio niert Ethernet Schnittstelle Z auf der Oberseite Ethernet Patch Kabel mit RJ45 Steckverbinder oder Y Kabel bei Nutzung des Ethernet Switches GEFAHR Gefahr durch hohe Berührungsspannungen Nichtbeachtung hat Tod oder schwere Körperver l...

Page 24: ...J 1 RS485 Serielle Schnittstelle FO Lichtwellenleiter Schnittstelle Q IKanal 1 I1 Kanal 1 Strommessung Pluspol Pinnummer 2 Minuspol Pinnummer 1 Q IKanal 2 I2 Kanal 2 Strommessung Pluspol Pinnummer 6 Minuspol Pinnummer 4 Q IKanal 3 I3 Kanal 3 Strommessung Pluspol Pinnummer 3 Minuspol Pinnummer 5 Q IKanal 4 I4 Kanal 4 Strommessung Pluspol Pinnummer 7 Minuspol Pinnummer 9 Q IKanal 5 I5 Kanal 5 Stromm...

Page 25: ...Strommessung Pluspol Pinnummer 6 Minuspol Pinnummer 4 T IKanal 3 I3 Kanal 3 Strommessung Pluspol Pinnummer 3 Minuspol Pinnummer 5 T IKanal 4 I4 Kanal 4 Strommessung Pluspol Pinnummer 7 Minuspol Pinnummer 9 T IKanal 5 I5 Kanal 5 Strommessung Pluspol Pinnummer 11 Minuspol Pinnummer 13 T IKanal 6 I6 Kanal 6 Strommessung Pluspol Pinnummer 15 Minuspol Pinnummer 17 Z Ethernet Schnittstelle Ethernet Ansc...

Page 26: ...ei betriebsinternem Bedarf Eine ausführliche Beschreibung des Geräteabgleichs finden Sie im Gerätehandbuch der SICAM AI Unit 7XV5674 Bestellnummer E50417 G1100 C492 WARNUNG Warnung vor Unfällen bei Benutzung von ungeeig netem Werkzeug Nichtbeachtung kann Tod oder schwere Körperverlet zung zur Folge haben Beachten Sie bei den Arbeiten unbedingt die Festle gungen und Durchführungsanweisungen der Unf...

Page 27: ... oder Verwendung eines falschen Batterietyps Nichtbeachtung kann Tod oder schwere Körperver letzung zur Folge haben Der Einbau und Austausch der Batterie darf nur von elektrotechnisch qualifiziertem Personal vorgenom men werden das mit den Sicherheitsbestimmungen und Vorsichtsmaßnahmen vertraut ist und diese befolgt Die Lithium Batterie dürfen Sie nur durch den Typ PANASONIC CR2032 oder VARTA 6032...

Page 28: ...ie Batterie aus der Batteriefassung 3 Entsorgen Sie die Batterie gemäß dem Hinweis auf der nächsten Seite 4 Entnehmen Sie die neue Batterie des Typs PANASONIC CR2032 oder VARTA 6032 101 501 der Verpackung auf der Verpackung aufgedrucktes Verbrauchsdatum beachten 5 Setzen Sie die Batterie vorsichtig unter Beachtung Batteriefach deckel WARNUNG Warnung vor Explosionsgefahr bei nicht vollständig entla...

Page 29: ...tteriefachdeckel in richtiger Ein baulage wieder in das Gehäuse HINWEISE zur Batterie Entsorgung Die im Gerät befindliche Batterie enthält Lithium und darf nur durch Fachpersonal ausgewechselt und durch entsprechende Recyclingbetriebe entsorgt werden Werfen Sie die Batterie nicht in den Abfall Bei der Entsorgung der Batterie sind die nationalen und internationalen Bestimmungen einzuhalten ...

Page 30: ...gnalisieren den aktuellen Gerätezustand Bezeichnung der LEDs Bild 14 1 Bezeichnung der LEDs Bedeutung der LEDs LED grün rot gelb ein LED grün rot gelb blinkt LEDs H1 H2 ERROR gemäß Parametrierung LED aus Ethernet Switch ausgeschaltet LED Speed gelb aus ein 10 100 MBit s LED Link Activity grün leuchtet Ethernet Link vorhanden blinkt Ethernet Link vorhanden Datentransfer aus keine Ethernet Partner a...

Page 31: ...LED Link Activity Kanal 2 grün leuchtet Ethernet Link vorhanden blinkt Ethernet Link vorhanden Datentransfer aus keine Ethernet Partner angeschlossen LEDs Bedeutung Gerät ausgeschaltet Keine Firmware geladen Boot Programm IP Addr Tastschalter während des Einschaltens der Versorgungsspannung gedrückt RUN ERROR H1 H2 RUN ERROR H1 H2 RUN ERROR H1 H2 ...

Page 32: ...Drücken des IP Addr Tastschalters Boot Programm gestartet es existiert keine Prozessapplikation DHCP aktiv H1 schaltet aus nach Empfang der IP Adresse über DHCP Default IP Adresse durch Drücken des IP Addr Tastschalters Boot Programm wurde gestartet weil Fehler in der Prozessapplikation auftrat DHCP aktiv H1 schaltet aus nach Empfang der IP Adresse über DHCP LEDs Bedeutung RUN ERROR H1 H2 RUN ERRO...

Page 33: ...e oder IP Adresse über DHCP bezogen Parametrierung der ERROR LED siehe Gerätehandbuch DHCP LED RUN grün leuchtet nachdem IP Adresse von DHCP Server empfangen Default IP Adresse wurde mittels Drücken des IP Addr Tasters übernommen Doppelte IP Adresse wurde erkannt LEDs Bedeutung RUN ERROR H1 H2 RUN ERROR H1 H2 RUN ERROR H1 H2 C C RUN ERROR H1 H2 C C ERROR RUN H1 H2 C C C ERROR ERROR RUN H1 H2 C C E...

Page 34: ...esetzt sind die nach den Richtlinien für elektrostatisch gefährdete Bauelemente EGB aus schließlich durch den Hersteller zu behandeln sind Außerdem können gefährliche Spannungen bei unkor rekter Arbeitsweise zu tödlichen Verletzungen führen Sollten Sie einen Defekt vermuten empfehlen wir das komplette Gerät ins Herstellerwerk einzusenden Hierzu verwenden Sie möglichst die Original Trans portverpac...

Page 35: ...ge setzten Elektrolytkondensatoren zu formieren Ebenso sollten Sie vor einem geplanten Einsatz des Gerätes verfahren Beachten Sie hierzu unbedingt die Hinweise zur Inbetriebnahme im Kapitel 8 Die Lithium Batterien unserer Geräte erfüllen die inter nationalen Voraussetzungen der Gefahrgutvorschriften für die verschiedenen Verkehrsträger Sonderbestim mung 188 aus den UN Empfehlungen für den Trans po...

Page 36: ...ge für Gleichstrommessungen Nenneingangsstrombereiche DC 0 mA bis 20 mA DC 4 mA bis 20 mA Max Eingangsspannung 5 V bei Gleichstrommessung Max Eingangsleistung 150 mW pro Kanal Eingangswiderstand 140 Ω HINWEIS Weitere Angaben zu den technischen Daten sind im Gerätehandbuch SICAM AI Unit 7XV5674 Bestellnummer E50417 G1100 C492 enthalten ...

Page 37: ...ngungen Eingangsstrom der Referenzquelle Nennstrom 0 02 Umgebungstemperatur 23 C 1 C Versorgungsspannung UHN 5 Anwärmzeit 15 min Fremdfelder keine Ein Ausgänge Isolierung Nenn spannung ISO Prüf spannung Kate gorie Strom messeingänge verstärkt 50 V AC 2 6 kV DC 3 6 kV Kat III Versorgungs spannung verstärkt 300 V DC 3 125 kV Kat III Ethernet Schnittstelle Funktion 50 V DC 700 V Kat III RS485 Schnitt...

Page 38: ... für 100Base T 100 Ω bis 150 Ω STP CAT6 Max Kabellänge 100Base T 100 m Spannungsfestigkeit DC 700 V 17 5 Serielle Schnittstelle RS485 und Optisch Verbindungen RS485 9 poliger D Sub Buchse Max Leitungslänge 1000 m 3 adrig verdrillt geschirmt Optisch LWL ST Verbindungs stecker 820 nm Max LWL Kabellänge 2000 m bei 62 5 125 μm Multimode LWL Empfängerempfindlichkeit 24 dBm bei 62 5 125 μm LWL Optisches...

Page 39: ...00 Bit s 19 200 Bit s 38 400 Bit s 57 600 Bit s 115 200 Bit s Parität Keine 1 Stopp Bit Gerade Ungerade Keine 2 Stopp Bit Protokoll Halbduplex Max Kabellänge 1000 m Busprotokoll SIPROTEC RTU 20 mA Baud Rate 4800 Bit s 9600 Bit s 19 200 Bit s 38 400 Bit s Parität Keine 1 Stopp Bit Gerade Ungerade Keine 2 Stopp Bit Protokoll Halbduplex Max Kabellänge 1000 m ...

Page 40: ...frequenz 45 Hz bis 65 Hz Zulässige Eingangsspan 20 nungstoleranz gilt für alle Eingangsspannungen Maximale Leistungsaufnahme 5 W 16 VA 17 7 Batterie Typen PANASONIC CR2032 VARTA 6032 101 501 Spannung 3 V Kapazität 230 mAh Typische Lebensdauer bei ständig angelegter Versorgungsspannung 10 Jahre bei nicht ständig angelegter Versorgungsspannung 2 Monate innerhalb von 10 Jahren ...

Page 41: ... der Lagerung 25 C bis 70 C Mittlere relative Luftfeuchte 75 Kondensation im Betrieb Nicht zulässig während Transport und Lagerung Zulässig 17 9 Zusätzliche technische Daten Interne Sicherung nicht austauschbar Typ T1 6A 250V gemäß IEC 60127 Interne Sicherung sekundär nicht austauschbar Typ F2A 125V gemäß UL 248 14 17 10 Schutzklasse gemäß IEC 60529 Klemmenseite IP20 Hutschienenseite IP20 Oberseit...

Page 42: ...information E50417 B1150 C492 A1 Ausgabestand 09 2012 17 11 Maße Masse ca 0 5 kg Abmessungen B x H x T 96 mm x 96 mm x 100 mm Bild 17 1 Abmessungen 1 Maßbild gilt für Hutschiene DIN EN 50022 35 x 7 5 120 1 110 9 127 61 Maßangabe in mm ...

Page 43: ...E50417 B1150 C492 A1 SICAM AI Unit 20 mA Input Acquisition Device 7XV5674 Product Information ...

Page 44: ...ity EMC Council Directive 2004 108 EC and concerning elec trical equipment for use within specified voltage limits Low voltage Directive 2006 95 EC This conformity has been established by means of tests con ducted by Siemens AG in accordance of the Council Direc tive in agreement with the generic standards EN 61000 6 2 and EN 61000 6 4 for the EMC directives and with the stan dard EN 61010 1 for t...

Page 45: ...afety 6 4 Used Symbols 9 5 Ordering Information 10 6 Application 11 7 Design 13 8 Mounting and Commissioning 15 9 Connection Type 20 10 Measurands and Calculated Measurands 21 11 Interfaces 22 12 Calibration 26 13 Replacing the Battery 27 14 LED Indications 30 15 Troubleshooting and Repair 34 16 Storage and Transport 35 17 Technical Data Selection 36 ...

Page 46: ... AG shall not assume any liability for defects and damage which result through use of the information contained herein This content does not form part of a contract or of busi ness relations nor does it change these All obligations of Siemens AG are stated in the relevant contractual agreements Siemens AG reserves the right to revise this document from time to time Copyright Copyright Siemens AG 2...

Page 47: ... area of automation engineering To ensure the safe installation commissioning operation and maintenance of the devices described in this document personnel must be familiar with and practice the safety instructions and warnings in this document correctly Only electrically qualified personnel see Personnel qualified in electrical engineering have the special knowledge required to interpret the gene...

Page 48: ...gy Customer Support Center is available to you twenty four hours a day Phone 49 1805 24 8437 Fax 49 1805 24 2471 Internet http www siprotec de e mail support ic siemens com 3 Information for Your Safety These Product Information do not list all the safety measures required to operate the equipment module device since specific operating conditions may make additional measures necessary However they...

Page 49: ...aken Follow all advice instructions to prevent death or severe injury CAUTION Caution means that minor or moderate injury can occur if the appropriate safety measures are not taken Follow all advice instructions to prevent minor injury NOTICE Notice means that damage to property can occur if the appropriate safety measures are not taken Follow all advice instructions to prevent damage to property ...

Page 50: ... party devices and components these must be recommended or approved by Siemens If the device is not used in accordance with this Product Information the scheduled protection is impaired Correct and safe operation of the product requires ade quate transportation storage installation and assem bly as well as appropriate use and maintenance During the operation of electric equipment it is unavoidable...

Page 51: ...xceeded this also refers to testing and commissioning 4 Used Symbols Table 4 1 Used Symbols No Symbol Description 1 Direct current IEC 60417 5031 2 Alternating current IEC 60417 5032 3 Direct current and alternating current IEC 60417 5033 4 Earth ground terminal IEC 60417 5017 5 Protective conductor terminal IEC 60417 5019 6 Caution risk of electric shoc 7 Caution risk of danger ISO 7000 0434 ...

Page 52: ...20 mA protocol 820 nm optical interface ST connector 4 Serial Modbus RTU and SIPROTEC 20 mA protocol 4 0 K Ethernet interface for Web Server and Modbus TCP 1 Ethernet interface for Web Server IEC 61850 and Modbus TCP 2 Serial interface and communication protocol Ethernet interface and communication protocol Twelve 20 mA inputs DIN rail mounting unit without display IP20 Case 96 mm x 96 mm x 100 mm...

Page 53: ...lds Protection SCADA DMS EMS systems GIS Gas Insulated Switchgear gas pressure monitoring Other industrial processes For example 4 mA to 20 mA signals coming from trans ducers monitoring of power temperatures pressure position are delivered over standard protocol for fur ther processing as visualization or connection to other automation processes The DC inputs from SICAM AI Unit 7XV5674 can be par...

Page 54: ...rface as RS485 or optical interface sup ports the following functions Transmission of measured data Transmission of indications Time synchronization via fieldbus Depending on the device version you can use either the Modbus RTU or the SIPROTEC RTU 20 mA communication protocol The integrated Web server allows the user to configure the parameters via HTML pages using a Web browser With the Ethernet ...

Page 55: ...s the RJ45 Ethernet connector with 2 LEDs and 4 additional LEDs At the cover of the battery compartment there is a labelling strip for the configurable LEDs H1 H2 ERROR and a battery symbol that indicates the polarity The type plate is also located on the top side and provides among other information the most important rated data of the device The lithium battery is located under the removable cov...

Page 56: ...bed in Chapter 11 Figure 7 2 DIN Rail Side of SICAM AI Unit 7XV5674 The snap on unit is mounted in the center of the DIN rail side The IP Addr push button is located in the lower right part If necessary it can be pressed 3 s to adjust the factory set default IP address The IP address and the standard subnet mask are imprinted on the side panel see Figure 7 2 Mount for snap on unit push button IP A...

Page 57: ...ctor cross sections of 1 5 mm AWG 16 to 2 5 mm AWG 14 max The terminal of the 20 mA inputs T and Q are designed for conductor cross sections of 0 2 mm AWG 24 to 1 5 mm AWG 16 max The device must not be exposed to condensation during operation The device must be installed in a location where it is not exposed to direct sunlight and strong temperature variations DANGER Danger due to high voltages No...

Page 58: ...DIN rail 1 Pull down the release device at the snap on clip and hold it in this position 2 Slide the device with the guiding of the snap on clip on to one side of the DIN rail 3 Move the device into the desired position on the DIN rail 4 Release the release device The device is now firmly mounted on the DIN rail Release device Pulling direction Snap on clip Guiding of the snap on clip DIN rail ...

Page 59: ...its guiding DANGER Danger due to high voltages Non observance will lead to death or serious injury Work may only be carried out by trained personnel see Preface who are familar with and observe the safety requirements and precautions Work may never be carried out if there is any dangerous voltage present De energize the device Circuit breaker A suitable isolating device shall be con nected upstrea...

Page 60: ... switch on the supply voltage verify that the operational data match the rated data on the name plate and the technical data according to Chapter 17 This applies in particular to the supply voltage VH and to the maximum current and voltage values of the device After an operating time of approximately 15 minutes the device will stay within the tolerances specified in the technical data The delivery...

Page 61: ... g precision engineer screwdriver 2 0 mm Figure 8 2 Device Top Side 2 Remove the battery 3 Remove the insulation from the battery 4 Insert the battery with the polarity indicated on the cover of the battery compartment 5 Close the cover Cover of the battery Polarity of Name plate the battery compartment NOTE Chapter 13 describes how to replace and handle the battery ...

Page 62: ...1150 C492 A1 Edition 09 2012 8 5 Setting the Parameters 9 Connection Type NOTE The parameterization is described in the device manual order number E50417 G1140 C492 NOTE The connection type is described in the device manual order number E50417 G1140 C492 ...

Page 63: ...he mean value window begins always to the full 10s 2 The mean value window begins always to the full 1min 3 The mean value window begins always to the full 1h 4 The mean value window begins always at 0 o clock device time Measurand Circuit Measuring Range Tolerance limits 1 Direct current IDC Channel 1 to 12 current measurement 0 mA to 20 mA 4 mA to 20 mA 0 2 Measurand Calculated Measurand Measuri...

Page 64: ...inal H amounts to 1 5 mm AWG 16 to 2 5 mm AWG 14 without bootlace ferrule 1 5 mm AWG 16 with bootlace ferrule Tightening torque 0 4 Nm to 0 5 Nm 3 5 in lb to 4 5 in lb SICAM AI Unit with DC Inputs and RS485 Interface D sub Socket SICAM AI Unit with DC Inputs and Optical Interface ST connector NOTE The device is provided with Phoenix FMC 1 5 9 ST 3 81 plug connector for the T and Q connections ...

Page 65: ...674 0KK30 xAA1 RS485 cable with the plug connector D sub socket 9 pin 820 nm optical interface J on the terminal side of 7XV5674 0KK40 xAA1 FO cable fitted with ST connector Ethernet interface Z on the top side Ethernet patch cable with RJ45 plug connector or Y cable if an Ethernet switch is used DANGER Danger due to high voltages Non observance will lead to death or serious injury The grounding o...

Page 66: ...e FO Fiber optic interface Q IChannel 1 I1 Channel 1 current measurement Positiveterminal pinnumber2 Negative terminal pin number 1 Q IChannel 2 I2 Channel 2 current measurement Positiveterminal pinnumber6 Negative terminal pin number 4 Q IChannel 3 I3 Channel 3 current measurement Positiveterminal pinnumber3 Negative terminal pin number 5 Q IChannel 4 I4 Channel 4 current measurement Positiveterm...

Page 67: ...easurement Positiveterminal pinnumber6 Negative terminal pin number 4 T IChannel 3 I3 Channel 3 current measurement Positiveterminal pinnumber3 Negative terminal pin number 5 T IChannel 4 I4 Channel 4 current measurement Positiveterminal pinnumber7 Negative terminal pin number 9 T IChannel 5 I5 Channel 5 current measurement Positiveterminal pinnumber11 Negative terminal pin number 13 T IChannel 6 ...

Page 68: ...ut if necessary due to internal requirements For a detailed description of the device calibration see the device manual of SICAM AI Unit 7XV5674 order number E50417 G1140 C492 WARNING Warning accidents can occur by using inappropriate tools Non observance may lead to death or serious injury When carrying out work it is essential that you observe the regulations and instruction guidelines of accide...

Page 69: ...nce may lead to death or serious injury Installing the battery or replacing it may only be car ried out by trained personnel see preface who are familiar with and observe the safety requirements and precautions Do not reverse the polarity of the battery Do not attempt to open the battery Do not attempt to recharge the battery Servicing of the circuitry involving the batteries and replacement of th...

Page 70: ...tweezers to pull the battery out of the compartment 3 Dispose of the battery as explained on the next page 4 Remove the new battery type PANASONIC CR2032 or VARTA 6032 101 501 from the packaging check the expiry date on the packaging 5 Insert the battery carefully into the battery compartment with the polarity indicated above the Cover of battery compartment WARNING Warning of explosion hazard in ...

Page 71: ...g and make sure it is in the correct position NOTES on battery disposal The battery used in this device contains lithium It may only be replaced by qualified personnel and disposed of by authorized recycling companies Do not dispose of the battery in the regular household waste The national and international regulations must be observed when disposing of the battery ...

Page 72: ...ndicate the current device status Designation of the LEDs Figure 14 1 Designation of the LEDs Meaning of the LEDs LED green red yellow on LED green red yellow flashes LEDs H1 H2 ERROR according to parameterization LED off Ethernet switch turned off LED Speed yellow off on 10 100 Mbit s LED Link Activity green lit Ethernet link is up flashes Ethernet link is up data transfer off no Ethernet partner...

Page 73: ... Activity channel 1 yellow LED Link Activity channel 2 green lit Ethernet link is up flashes Ethernet link is up data transfer off no Ethernet partners connected LEDs Meaning Device switched off No firmware loaded Boot loader IP Addr push button pressed during power on RUN ERROR H1 H2 RUN ERROR H1 H2 RUN ERROR H1 H2 ...

Page 74: ...sh button Boot loader started no process application exists DHCP active H1 switches off after reception of the IP address via DHCP Default IP address by pressing the IP Addr push button Boot loader was started because an error occurred in the process application DHCP active H1 switches off after reception of the IP address via DHCP LEDs Meaning RUN ERROR H1 H2 RUN ERROR H1 H2 RUN ERROR H1 H2 RUN E...

Page 75: ...r obtained by DHCP Parameter setting of the ERROR LED see device manual DHCP LED RUN green is lit after the IP address was received by the DHCP server Default IP address was applied by pressing the IP Addr push button Double IP address detected LEDs Meaning RUN ERROR H1 H2 RUN ERROR H1 H2 RUN ERROR H1 H2 C C RUN ERROR H1 H2 C C ERROR RUN H1 H2 C C C ERROR ERROR RUN H1 H2 C C ERROR RUN ERROR H1 H2 ...

Page 76: ...lectronic components that may only be handled by the manufacturer in compliance with the regulations for electrostatic sensitive devices ESD Furthermore hazardous voltages can lead to lethal injuries when the work is performed improperly If you suspect that the device has a defect Siemens recommends to send the entire device back to the manufacturer If possible use the original transport packaging...

Page 77: ...once a year to reform the electrolytic capacitors in the device This procedure should also be carried out before operating the device In this context pay attention to the commissioning notes in Chapter 8 The Lithium batteries in our equipment are subject to Special Provision 188 of the UN Recommendations on the Transport of Dangerous Goods Model Regulations and Special Provision A45 of the IATA Da...

Page 78: ...ts for direct current measurements Rated input current ranges DC 0 mA to 20 mA DC 4 mA to 20 mA Maximum input voltage 5 V at DC measurements Maximum input power 150 mW per channel Input impedance 140 Ω NOTE For more information about the technical data see the Device Manual SICAM AI Unit 7XV5674 order number E50417 G1140 C492 ...

Page 79: ...of reference soure Rated current 0 02 Ambient temperature 23 C 1 C Supply voltage VHN 5 Warm up time 15 min Interfering fields none Inputs outputs Insulation Rated voltage Insulation test voltage Category Current measuring inputs Reinforced 50 V AC 2 3 kV DC 3 6 kV Cat III Supply voltage Reinforced 300 V DC 3 125 kV Cat III Ethernet interface Function 50 V DC 700 V Cat III RS485 interface Function...

Page 80: ...00Base T RJ45 Cable for 100Base T 100 Ω to 150 Ω STP CAT6 Max cable length 100Base T 100 m Voltage strength DC 700 V 17 5 Serial Interface RS485 and Optical Connections RS485 9 pin D sub socket Maximum line length 1000 m three wire twisted shielded Optical ST connector 820 nm Maximum FO cable length 2000 m at 62 5 125 μm FO Receiver sensitivity 24 dBm at 62 5 125 μm FO Optical budget min 8 dB at 6...

Page 81: ...bit s 9600 bit s 19 200 bit s 38 400 bit s 57 600 bit s 115 200 bit s Parity None 1 stop bit Even Odd None 2 stop bit Protocol Half duplex Max cable length 1000 m Bus protocol SIPROTEC RTU 20 mA Baud rate 4800 bit s 9600 bit s 19 200 bit s 38 400 bit s Parity None 1 stop bit Even Odd None 2 stop bit Protocol Half duplex Max cable length 1000 m ...

Page 82: ... 250 V Frequency at AC 45 Hz to 65 Hz Admissible input voltage 20 tolerance applies to all input voltages Maximum power consumption 5 W 16 VA 17 7 Battery Types PANASONIC CR2032 VARTA 6032 101 501 Voltage 3 V Capacity 230 mAh Typical life time at permanently available power supply 10 years at not permanently available power supply 2 month within 10 years ...

Page 83: ...during storage 25 C to 70 C 13 F to 158 F Mean relative air humidity 75 Condensation during operation Not permitted during transport and storage Permitted 17 9 Additional Technical Data Internal fuse not replaceable type T1 6A 250V acc to IEC 60127 Internal fuse secondary not replaceable type F2A 125V acc to UL 248 14 17 10 Protection class according to IEC 60529 Terminal side IP20 DIN rail side I...

Page 84: ... Edition 09 2012 17 11 Dimensions Mass about 0 5 kg Dimensions W x H x D 96 mm x 96 mm x 100 mm 3 78 in x 3 78 in x 3 94 in Figure 17 1 Dimensions 1 Dimensional drawing is valid for DIN rail DIN EN 50022 35 x 7 5 120 1 4 73 110 9 4 37 127 61 5 02 Dimensions in mm in ...