17
SICAM AI Unit 7XV5674, Product Information
E50417-B1150-C492-A1, Edition 09.2012
UL-certification conditions
Field Wires of Control Circuits shall be separated from
other circuits with respect to the end use requirements!
8.3
Electrical Connection
NOTE
The snap-on clip is adjusted to a certain height setting
by the manufacturer. You can change this position if
necessary. To do so, lever the release device out of its
guiding (no special tool required) and move the release
device into the desired position. Subsequently, press
the release device back into its guiding.
DANGER
Danger due to high voltages
Non-observance will lead to death or serious injury.
Work may only be carried out by trained personnel (see
Preface) who are familar with and observe the safety
requirements and precautions.
Work may never be carried out if there is any dangerous
voltage present.
De-energize the device.
Circuit breaker:
A suitable isolating device shall be con-
nected upstream in order to permit disconnection of the
device from the power supply. The circuit breaker must
be mounted close to the device, be easily accessible to
the user and marked as a circuit breaker for the device.
Secure the supply voltage with an approved (UL/IEC)
fuse: 1.6 A, type C.
If a melting fuse is used, a suitable approved (UL/IEC)
fuse holder has to be used.