Connection
Screw Terminals for the Junction Blocks
The terminal screws are slotted screws that can be turned with a 0.3 x 3.5 or 0.6 x 3.5 screwdriver. The tighte-
ning torque for all terminal screws is 0.4 Nm to 0.5 Nm and 1.2 Nm for all grounding screws.
The following screw connections are available (see
Junction block for the signal line
2-phase
Junction block for the signal Life Contact
3-phase
Junction block for the auxiliary voltage V
aux
2-phase
Strip the insulation from the connection wires at a length of 9 mm, guide them into the screw terminal as far
as they will go and secure them in such a way that they cannot be pulled out again when they are being
fastened into place. After screwing them on, check that the connections are fitted properly.
Voltage Connections
i
i
NOTE
Connect a suitable disconnecting device upstream to de-energize the device.
Install the disconnecting device near the device and secure it with a 6-A fuse. The disconnecting device
must be easily accessible to the user and marked as a disconnecting device for the device.
Use the following cables:
•
Solid conductors or stranded-wire conductors for cross-sections from 0.2 mm
2
to 2.5 mm
2
in accordance
with AWG 14 to 24
•
Stranded-wire conductors with bootlace ferrules for cross-sections from 0.25 mm
2
to 1.5 mm
2
in accor-
dance with AWG 16 to 23
i
i
NOTE
Use copper conductors only.
Signal Connections - Line
Direct Connection
Use the following cables:
•
Solid conductors or stranded-wire conductors for cross-sections from 0.2 mm
2
to 2.5 mm
2
in accordance
with AWG 14 to AWG 24
•
Stranded-wire conductors with bootlace ferrules for cross-sections from 0.25 mm
2
to 1.5 mm
2
in accor-
dance with AWG 16 to AWG 23
If a stranded-wire conductor is used with a smaller cross-section (min. AWG 26), the connection to the screw
terminal must be established using an appropriate aid (bootlace ferrule).
FO Connections
) are provided with shielding caps that prevent pollution. They can be
removed by rotating them 90° to the left.
4.2
4.2.1
4.2.2
4.2.3
4.2.4
Assembly and Commissioning
4.2 Connection
Accessories, Communication Converter - Copper/Synchronous Interface, Manual
27